Technical data
70 OM 1191
Fieldbus Adapter
System Control
Usingtheeldbusformiscellaneousdrivecontrolrequires: • Driveparametervaluessetasdenedbelow.
• Fieldbus controller command(s) in the appropriate
location.(ThelocationisdenedbytheProtocol
Reference, which is protocol dependent.)
Table 45: Fieldbus Controller Commands
Drive Parameter Value Description Protocol Reference
1601 RUN ENABLE 7 (COMM) Run enable by eldbus.
1604 FAULT RESET SEL 8 (COMM) Fault reset by eldbus.
1607 PARAM SAVE 1 (SAVE
Saves altered parameters to memory (then value returns to 0).
Relay Output Control
Usingtheeldbusforrelayoutputcontrolrequires: • Driveparametervaluessetasdenedbelow.
• Fieldbus controller supplied, binary coded, relay
command(s) in the appropriate location. (The location
isdenedbytheProtocolReference,whichisprotocol
dependent.)
Table 46: Relay Output Control
Drive Parameter Value Description Protocol Reference
1401 RELAY OUTPUT 1
35 (COMM)
36 (COMM(-1))
Relay Output 1 controlled by eldbus.
1402 RELAY OUTPUT 2 Relay Output 2 controlled by eldbus.
1403 RELAY OUTPUT 3 Relay Output 3 controlled by eldbus.
1410
1
RELAY OUTPUT 4 Relay Output 4 controlled by eldbus.
1411
1
RELAY OUTPUT 5 Relay Output 5 controlled by eldbus.
1412
1
RELAY OUTPUT 6 Relay Output 6 controlled by eldbus.
0122 RO 1-3 STATUS Relay 1…3 status.
0123 RO 4-6 STATUS Relay 4…6 status.
1. More than 3 relays requires the addition of a relay extension module.
NOTE: Note: Relay status feedback occurs without
conguration as dened below.
Analog Output Control
Usingtheeldbusforanalogoutputcontrol(e.g.PIDsetpoint)
requires:
• Driveparametervaluessetasdenedbelow.
• Fieldbus controller supplied analog value(s) in the
appropriatelocation.(Thelocationisdenedbythe
Protocol Reference, which is protocol dependent.)
Table 47: Analog Output Control
Drive Parameter Value Description Protocol Reference
1501 AO1 CONTENT SEL 135 (COMM VALUE 1)
Analog Output 1 controlled by writing to parameter 0135.
—
0135 COMM VALUE 1 —
1502…1505
AO1 CONTENT MIN…
MAXIMUM AO1
Set appropriate values.
Used for scaling —
1506 FILTER AO1
Filter time constant for AO1. —
1507 AO2 CONTENT SEL 136 (COMM VALUE 2)
Analog Output 2 controlled by writing to parameter 0136.
—
0136 COMM VALUE 2 —
1508…1511
AO2 CONTENT MIN…
MAXIMUM AO2
Set appropriate values.
Used for scaling —
1512 FILTER AO2
Filter time constant for AO2. —