Technical data

OM 1191 69
Fieldbus Adapter
Communication Setup – FBA
Serial Communication Selection
Toactivatetheserialcommunication,useparameter9802
COMMPROTOCOLSEL.Set9802=4(EXTFBA).
Serial communication conguration
Setting9802,togetherwithmountingaparticularFBA
module, automatically sets the appropriate default values in
parametersthatdenethecommunicationprocess.These
parametersanddescriptionsaredenedintheuser’smanual
supplied with the FBA module.
NOTE: This is not required with MicroTech III controls.
• Parameter5101isautomaticallycongured.
Parameters 5102…5126 are protocol-dependent and
dene,forexample,theproleused,andadditional
I/O words. These parameters are referred to as the
eldbuscongurationparameters.Seetheuser’smanual
providedwiththeFBAmodulefordetailsontheeldbus
congurationparameters.
Parameter 5127 forces the validation of changes to
parameters 5102…5126. If parameter 5127 is not used,
changes to parameters 5102…5126 take affect only after
the drive power is cycled.
Parameters 5128…5133 provide data about the FBA
module currently installed (e.g. component versions and
status).
The Parameters section lists the group 51 parameters.
Activate Drive Control Functions – FBA
Fieldbus control of various drive functions requires
congurationto:
• Tellthedrivetoaccepteldbuscontrolofthefunction.
• Deneasaeldbusinput,anydrivedatarequiredfor
control.
• Deneasaeldbusoutput,anycontroldatarequiredby
the drive.
The following sections describe, at a general level, the
congurationrequiredforeachcontrolfunction.Thelast
column in each table below is deliberately blank. See
the user’s manual supplied with the FBA module for the
appropriate entry.
Start/Stop Direction Control
Usingtheeldbusforstart/stop/directioncontrolofthedrive
requires:
• Driveparametervaluessetasdenedbelow.
Fieldbus controller supplied command(s) in the
appropriatelocation.(Thelocationisdenedbythe
Protocol Reference, which is protocol dependent.)
Table 43: Start/Stop/Direction Control
Drive Parameter Value Description Protocol Reference
1001 EXT1 COMMANDS 10 (COMM) Start/Stop controlled by eldbus with Ext1 selected.
1002 EXT2 COMMANDS 10 (COMM) Start/Stop by controlled eldbus with Ext2 selected.
1003 DIRECTION 3 (REQUEST) Direction controlled by eldbus.
Input Reference Select
Usingtheeldbustoprovideinputreferencetothedrive
requires:
• Driveparametervaluesetasdenedbelow.
Fieldbus controller supplied reference word(s) in the
appropriatelocation.(Thelocationisdenedbythe
Protocol Reference, which is protocol dependent.)
NOTE: Multiple references are supported only when using
the Daikin Drives profile.
Scaling
Where required, REFERENCES can be scaled. See the
Reference scaling in the following sections, as appropriate:
Daikindrivesprofiletechnicaldata
• Genericproletechnicaldata
Table 44: Input Reference
Drive Parameter Value Description Protocol Reference
1102 EXT1/EXT2 SEL 8 (COMM) Ref. selected by eldbus. (Required only if 2 references used.)
1103 REF1 SEL
8 (COMM)
9 (COMM+AI1)
10 (COMM*AI1)
Input reference 1 supplied by eldbus.
1106 REF2 SEL
8 (COMM)
9 (COMM+AI)
10 (COMM*AI)
Input reference 1 supplied by eldbus. (Required only if 2 references
used.)