Technical data
60 OM 1191
Embedded Fieldbus
Binary Value Object Instance Summary
The following table summarizes the Binary Value Objects supported:
Table 37: Binary Value Objects
Instance ID Object Name Description Active/Inactive Text
Present Value
Access Type
BV0 RUN/STOP ACT
This object indicates the drive Run Status, regardless of the control source. RUN/STOP R
BV1 FWD/REV ACT
This object indicates the motor’s rotation direction, regardless of the control source. REV/FWD R
BV2 FAULT ACT
this object indicates the drive’s fault status. FAULT/OK R
BV3 EXT 1/2 ACT
This object indicates which control source is active: External 1 or External 2. EXT2/EXT1 R
BV4 HAND/AUTO ACT
This object indicates whether the drive is under Hand or Auto control. HAND/AUTO R
BV5 ALARM ACT
This object indicates the drive’s alarm status. ALARM/OK R
BV6 MAINT REQ
This object indicates the drive’s maintenance status. Refer to Group 29 in the
drive’s parameter descriptions.
MAINT/OK R
BV7 DRIVE READY
This object indicates whether the drive is ready to accept a run command. READY/NOT READY R
BV8 AT SETPOINT
This object indicates whether the drive is at the commanded setpoint. YES/NO R
BV9 RUN ENA ACT
This object indicates the Run Enable command status, regardless of the control
source.
ENABLE/DISABLE R
BV10 RUN/STOP CMD
This object commands a drive start. Control requires either:
• Parameter 1001 value = COMM for control by EXT1 or
• Parameter 1002 value = COMM for control by EXT2.
RUN/STOP C
BV11 FWD/REV CMD
This object commands a motor rotation direction change. Control requires 1003 =
REQUEST and either:
• Parameter 1001 value = COMM for control by EXT1 or
• Parameter 1002 value = COMM for control by EXT2.
REV/FWD C
BV12 RUN ENA CMD
This object commands Run Enable. Control requires parameter 1601 value =
COMM.
ENABLE/DISABLE C
BV13 EXT 1/2 CMD
This object selects ext1 or ext2 as the active control source. Control requires
parameter 1102 value = COMM.
EXT2/EXT1 C
BV14 FAULT RESET
This object resets a faulted drive. The command is rising edge triggered. Control
requires parameter 1604 value = COMM.
RESET/NO C
BV15 MBOX READ
This object reads a parameter (dened by AV25 MBOX PARAM) and returns it in
AV26 MBOX DATA.
READ/RESET W
BV16 MBOX WRITE
This object writes the data value specied by AV26, MBOX DATA, to a parameter
(dened by AV25, MBOX PARAM).
WRITE/RESET W
BV17 LOCK PANEL
This object locks the panel and prevents parameter changes. The corresponding
drive parameter is 1602.
LOCK/UNLOCK W
BV18
CTL OVERRIDE
CMD
This object commands the drive into BACnet Control Override. In this mode,
BACnet takes drive control from the normal source. However, the control panel’s
HAND mode has priority over BACnet Control Override.
ON/OFF C
BV19
CTL OVERRIDE
ACT
This object indicates whether the drive is in BACnet Control Override. (See BV18.) ON/OFF R
BV20 START ENABLE 1
This object commands start enable1. Control requires param 1608 value = COMM. ENABLE/DISABLE C
BV21 START ENABLE 2
This object commands start enable1. Control requires param 1609 value = COMM. ENABLE/DISABLE C
NOTE: For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable. Commandable
values support priority arrays & relinquish defaults.
Analog Input Object Instance Summary
The following table summarizes the Analog Input Objects supported:
Table 38: Analog Input Objects
Instance ID Object Name Description Units
Present Value
Access Type
AI0 ANALOG INPUT 1
This object indicates the value of Analog Input 1. The corresponding drive parameter is 0120. Percent R
AI1 ANALOG INPUT 2
This object indicates the value of Analog Input 2. The corresponding drive parameter is 0121. Percen R
NOTE: For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable. Commandable
values support priority arrays & relinquish defaults.