Technical data

OM 1191 53
Embedded Fieldbus
Analog Output Control
Usingtheeldbusforanalogoutputcontrolrequires:
• Driveparametervaluessetasdenedbelow.
Fieldbus controller supplied reference word(s) in the
appropriatelocation.(Thelocationisdenedbythe
Protocol Reference, which is protocol dependent.)
Table 28: Analog Output Control Parameters
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
Daikin
DRV
DCU PROFILE
1501 AO1 CONTENT SEL
135 (COMM
VALUE 1)
Analog Output
1 controlled
by writing to
parameter 0135.
0135 COMM VALUE 1 40135 AO14 46 AO0
1507 AO2 CONTENT SEL
136 (COMM
VALUE 2)
Analog Output
2 controlled
by writing to
parameter 0136.
0136 COMM VALUE 2 40136 AO15 47 AO1
PID Control Setpoint Source
UsethefollowingsettingstoselecttheeldbusasthesetpointsourceforPIDloops:
Table 29: PID Control Setpoint Parameters
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
Daikin
DRV
DCU PROFILE
4010
SET POINT SEL
(Set 1)
8 (COMM VALUE 1)
9 (COMM + AI1)
10 (COMM*AI1)
Setpoint is either:
• Input Reference
2 (+/-/* AI1).
Control requires
parameter 1106
value = comm.
• Process PID
setpoint. Control
requires parameter
1106 value = pid1
out and parameter
4010 value =
comm.
40003 AO2 61 AV174110
SET POINT SEL
(Set 2)
4210
SET POINT SEL
(Ext/Trim)
Communication Fault
Whenusingeldbuscontrol,specifythedrivesactionifserialcommunicationislost.
Table 30: Communication Fault Parameters
Drive Parameter Value Description
3018 COMM FAULT FUNC
0 (NOT SEL)
1 (FAULT)
2 (CONST SP7)
3 (LAST SPEED)
Set for appropriate drive response.
3019 COMM FAULT TIME Set time delay before acting on a communication loss.