Technical data
46 OM 1191
Embedded Fieldbus
Embedded Fieldbus
Mechanical and Electrical Installation–EFB
WARNING
Connections should be made only while the drive is
disconnected from the power source.
• UseBelden9842orequivalent.Belden9842isadual
twisted, shielded pair cable with a wave impedance of
120Ω.
• Use one of these twisted shielded pairs for the RS485
link. Use this pair to connect all A (-) terminals together
and all B (+) terminals together.
• Use one of the wires in the other pair for the reference/
common (terminal 31), leaving one wire unused.
• Do not directly ground the RS485 network at any
point. Ground all devices on the network using their
corresponding earthing terminals.
• As always, the grounding wires should not form any
closed loops, and all the devices should be earthed to a
common ground.
• Connect the RS485 link in a daisy-chained bus, without
dropout lines.
• To reduce noise on the network, terminate the RS485
networkusing120Ωresistorsatbothendsofthe
network. Use the DIP switch to connect or disconnect
the termination resistors. See following wiring
diagram. The MD5 termination resistor (J-2) are active
terminators. This active circuit includes bins (“Pull-up”
and “Pull-down”) resistors.
• Connect the shield at each end of the cable to a drive.
On one end, connect the shield to terminal 28, and on
the other end connect to terminal 32. Do not connect
the incoming and outgoing cable shields to the same
terminals, as that would make the shielding continuous.
• Forcongurationinformationseethefollowing:
— Communication Setup – EFB on page 48.
— Activate Drive Control Functions – EFB on page
50..
Figure 7: Preferred Wiring Diagram