Technical data
34 OM 1191
Parameters
Group 34: Panel Display
Thisgroupdenesthecontentforcontrolpaneldisplay(middlearea),whenthecontrolpanelisintheOutputmode.
Table 18: Group 34: Panel Display
Code Description Range Resolution Default S
3401 SIGNAL1 PARAM 100…178 1
103
(OUTPUT
FREQ)
Selects the rst parameter (by number) displayed on the control panel.
• Denitions in this group dene display content when the control panel is in the control mode.
• Any parameter number in Group 01: OPERATING DATA can be selected.
• Using the following parameters, the display value can be scaled, converted to convenient units and/or
displayed as a bar graph.
• The gure identies selections made by parameters in this group.
• If just one or two parameters are selected for display, that is just one or two of the values of
parameters 3401 SIGNAL1 PARAM, 3408 SIGNAL2 PARAM and 3415 SIGNAL3 PARAM are other
than 100 (NOT SELECTED), the number and name of each displayed parameter are shown in
addition to the value.
100 = NOT SELECTED – First parameter not displayed.
101…178 – Displays parameter 0101…0178. If parameter does not exist, the display shows “n.a.”.
3404 OUTPUT1 DSP FORM 0…9 1
5 (+0.0)
Denes the decimal point location for the rst display parameter.
0…7 – Denes the decimal point location.
• Enter the number of digits desired to the right of the decimal point.
• See the table for an example using pi (3.14159).
8 = BAR METER – Species a bar meter display.
9 = DIRECT – Decimal point location and units of measure are identical to the source signal. See Group 01: Operating Data on page 13 parameter listing in
section Complete parameter list on page 1-67 for resolution (which indicates the decimal point location) and the units of measure.
3404 value Display Range
0 + 3.0 -32768…+32767 (Signed)
1 + 3.1
2 + 3.14
3 + 3.142
4 3.0 0…65535 (Unsigned)
5 3.1
6 3.14
7 3.142
8 Bar meter displayed.
9 Decimal point location and units as for the source signal.
3405 OUTPUT1 UNIT 0…127 1 121 (%SP)
Selects the units used with the rst display parameter.
Note:
Parameter is not effective if parameter 3404 OUTPUT1 DSP FORM = 9 (DIRECT).
0 = NO UNIT 9 = °C 18 = MWh 27 = ft 36 = l/s 45 = Pa 54 = lb/m 63 = Mrev
1 = A 10 = lb ft 19 = m/s 28 = MGD 37 = l/min 46 = GPS 55 = lb/h 64 = d
2 = V 11 = mA 20 = m3/h 29 = inHg 38 = l/h 47 = gal/s 56 = FPS 65 = inWC
3 = Hz 12 = mV 21 = dm3/s 30 = FPM 39 = m3/s 48 = gal/m 57 = ft/s 66 = m/min
4 = % 13 = kW 22 = bar 31 = kb/s 40 = m3/m 49 = gal/h 58 = inH2O 67 = Nm
5 = s 14 = W 23 = kPa 32 = kHz 41 = kg/s 50 = ft3/s 59 = in wg 68 = Km3/h
6 = h 15 = kWh 24 = GPM 33 = ohm 42 = kg/m 51 = ft3/m 60 = ft wg
7 = rpm 16 = °F 25 = PSI 34 = ppm 43 = kg/h 52 = ft3/h 61 = lbsi
8 = kh 17 = hp 26 = CFM 35 = pps 44 = mbar 53 = lb/s 62 = ms
The following units are useful for the bar display.
117 = %ref 119 = %dev 121 = % SP 123 = Iout 125 = Fout 127 = Vdc
118 = %act 120 = %LD 122 = %FBK 124 = Vout 126 = Tout