Technical data

16 OM 1191
Parameters
Table 5 continued: Group 01: Operating Data
0145 MOTOR TEMP
Par. 3501
= 1…3:
-10…200 °C
Par. 3501 =
4: 0…5000
ohm Par.
3501 =
5…6: 0…1
1
Motor temperature in degrees Celsius / PTC resistance in ohms.
Applies only if motor temperature sensor is set up.
0150 CB TEMP
-20.0…
150.0 °C
1.0 °C
Temperature of the drive control board in degrees Celsius.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the constant value of 25.0 °C.
0153 MOT THERM STRESS 0.0…100.0% 0.1%
Estimated rise of the motor temperature. Value equals to the estimated motor thermal stress as a percentage of the motor temperature trip level.
0158 PID COMM VALUE 1
-32768…
+32767
1
Data received from eldbus for PID control (PID1 and PID2).
0159 PID COMM VALUE 2
-32768…
+32767
1
Data received from eldbus for PID control (PID1 and PID2).
0174 SAVED KWH
0.0…999.9
kWh
0.1 kWh
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply. See the note on page 1-163.
• The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0.
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
0175 SAVED MWH
0…65535
MWh
1 MWh
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply. See the note on page 1-163.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
0176 SAVED AMOUNT 1
0.0…999.9 0.1
Energy saved in local currency (remainder when the total saved energy is divided by 1000). See the note on page 1-163.
• To nd out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the value of parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123.4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5 ×
1000 + 123.4 = 5123.4 currency units.
• The counter value is accumulated till it reaches 999.9 (the counter does not roll over).
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
• Local energy price is set with parameter 4502 ENERGY PRICE.
0177 SAVED AMOUNT 2 0…65535 1
Energy saved in local currency in thousand currency units. Eg value 5 means 5000 currency units. See the note on page 1-163.
• The counter value is accumulated till it reaches 65535 (the counter does not roll over).
• See parameter 0176 SAVED AMOUNT 1.
0178 SAVED CO
2
0.0…6553.5
tn
0.1 tn
Reduction of carbon dioxide emissions in tons. See the note on page 1-163.
• The counter value is accumulated till it reaches 6553.5 (the counter does not roll over).
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
• CO
2
conversion factor is set with parameter 4507 CO
2
CONV FACTOR.