Technical data
16 OM 1191
Parameters
Table 5 continued: Group 01: Operating Data
0145 MOTOR TEMP
Par. 3501
= 1…3:
-10…200 °C
Par. 3501 =
4: 0…5000
ohm Par.
3501 =
5…6: 0…1
1 —
Motor temperature in degrees Celsius / PTC resistance in ohms.
• Applies only if motor temperature sensor is set up.
0150 CB TEMP
-20.0…
150.0 °C
1.0 °C —
Temperature of the drive control board in degrees Celsius.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the constant value of 25.0 °C.
0153 MOT THERM STRESS 0.0…100.0% 0.1% —
Estimated rise of the motor temperature. Value equals to the estimated motor thermal stress as a percentage of the motor temperature trip level.
0158 PID COMM VALUE 1
-32768…
+32767
1 —
Data received from eldbus for PID control (PID1 and PID2).
0159 PID COMM VALUE 2
-32768…
+32767
1 —
Data received from eldbus for PID control (PID1 and PID2).
0174 SAVED KWH
0.0…999.9
kWh
0.1 kWh —
Energy saved in kWh compared to the energy used when the pump is connected directly to the supply. See the note on page 1-163.
• The counter value is accumulated till it reaches 999.9 after which the counter rolls over and starts again from 0.0.
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
0175 SAVED MWH
0…65535
MWh
1 MWh — —
Energy saved in MWh compared to the energy used when the pump is connected directly to the supply. See the note on page 1-163.
• The counter value is accumulated till it reaches 65535 after which the counter rolls over and starts again from 0.
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
0176 SAVED AMOUNT 1
0.0…999.9 0.1 —
Energy saved in local currency (remainder when the total saved energy is divided by 1000). See the note on page 1-163.
• To nd out the total saved energy in currency units, add the value of parameter 0177 multiplied by 1000 to the value of parameter 0176.
Example:
0176 SAVED AMOUNT 1 = 123.4
0177 SAVED AMOUNT 2 = 5
Total saved energy = 5 ×
1000 + 123.4 = 5123.4 currency units.
• The counter value is accumulated till it reaches 999.9 (the counter does not roll over).
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
• Local energy price is set with parameter 4502 ENERGY PRICE.
0177 SAVED AMOUNT 2 0…65535 1 —
Energy saved in local currency in thousand currency units. Eg value 5 means 5000 currency units. See the note on page 1-163.
• The counter value is accumulated till it reaches 65535 (the counter does not roll over).
• See parameter 0176 SAVED AMOUNT 1.
0178 SAVED CO
2
0.0…6553.5
tn
0.1 tn —
Reduction of carbon dioxide emissions in tons. See the note on page 1-163.
• The counter value is accumulated till it reaches 6553.5 (the counter does not roll over).
• Can be reset with parameter 4509 ENERGY RESET (resets all energy calculators at the same time).
• CO
2
conversion factor is set with parameter 4507 CO
2
CONV FACTOR.