Specifications

53
Cooling Only/ Cooling Mode (Heatpump)
Water Flow Rate = 1.02 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 8.69 8.32 8.05 7.78 7.35 6.92 6.49
SC 8.50 8.16 7.91 7.66 7.27 6.88 6.48
TC 9.02 8.62 8.33 8.04 7.56 7.09 6.61
SC 7.79 7.53 7.35 7.16 6.87 6.58 6.29
TC 9.45 9.01 8.70 8.39 7.85 7.31 6.77
SC 6.85 6.69 6.58 6.79 6.32 6.17 6.03
TC 9.56 9.17 8.89 8.61 8.10 7.59 7.08
SC 6.28 6.13 6.03 5.93 5.79 5.66 5.52
TC 9.88 9.63 9.45 9.28 8.86 8.45 8.04
SC 4.63 4.54 4.47 4.41 4.29 4.17 4.06
TC 9.98 9.78 9.64 9.50 9.12 8.74 8.36
SC 4.10 4.03 3.98 3.93 3.81 3.69 3.58
Water Flow Rate = 1.70 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 9.09 8.70 8.42 8.14 7.69 7.24 6.79
SC 8.89 8.53 8.27 8.02 7.60 7.19 6.78
TC 9.43 9.01 8.71 8.41 7.91 7.41 6.91
SC 8.15 7.88 7.68 7.49 7.19 6.88 6.58
TC 9.88 9.43 9.10 8.77 8.20 7.64 7.07
SC 7.16 6.99 6.88 7.10 6.61 6.46 6.31
TC 10.00 9.59 9.29 9.00 8.47 7.94 7.41
SC 6.56 6.41 6.31 6.21 6.06 5.91 5.78
TC 10.33 10.07 9.88 9.70 9.27 8.84 8.41
SC 4.84 4.75 4.68 4.61 4.48 4.36 4.24
TC 10.44 10.23 10.08 9.93 9.53 9.14 8.74
SC 4.29 4.21 4.16 4.10 3.98 3.86 3.74
Water Flow Rate = 2.38 m
3
/hr
Indoor, DB Indoor, WB Capacity
(°C) (°C) (kW) 13 20 25 30 35 40 45
TC 9.28 8.88 8.60 8.31 7.85 7.40 6.94
SC 9.08 8.71 8.45 8.19 7.77 7.35 6.93
TC 9.63 9.20 8.90 8.59 8.08 7.57 7.06
SC 8.32 8.05 7.85 7.65 7.34 7.03 6.72
TC 10.10 9.63 9.29 8.96 8.38 7.80 7.23
SC 7.31 7.15 7.03 7.26 6.75 6.60 6.44
TC 10.21 9.79 9.50 9.20 8.65 8.11 7.57
SC 6.71 6.55 6.44 6.34 6.19 6.04 5.90
TC 10.55 10.29 10.10 9.91 9.47 9.03 8.59
SC 4.95 4.85 4.78 4.71 4.58 4.45 4.33
TC 10.66 10.45 10.30 10.15 9.74 9.33 8.93
SC 4.38 4.30 4.25 4.19 4.07 3.95 3.83
Note:
1. DB = Dry Bulb, WB = Wet Bulb, TC = Total Capacity, SC = Sensible Capacity
2. All datas above are generated at delta T = Leaving Water Temperature - Entering Water Temperature = 5°C
23
24
15.5
17
19
20
Entering Water Temperature, (°C)
27.0
15.5
17
19
20
23
24
15.5
17
Entering Water Temperature, (°C)
27.0
Entering Water Temperature, (°C)
27.0
19
20
23
24
MWH 030B/BR