Heatpump Model (R22)
Model : M4RT200AR (Cooling Capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
46.473 45.013 43.709 42.405 41.102 40.058
SC
46.473 45.013 43.709 42.405 41.102 40.058
15 TC
51.333 49.081 47.071 45.061 43.051 41.444
SC
45.024 43.854 42.810 41.766 40.721 39.886
18 TC
64.585 60.177 56.241 52.305 48.370 45.221
SC
41.070 40.693 40.357 40.021 39.684 39.415
19.4 TC
70.770 65.355 60.520 55.686 50.851 46.984
SC
39.224 39.218 39.212 39.206 39.200 39.196
20 TC
73.420 67.704 62.601 57.498 52.394 48.311
SC
38.434 38.245 38.077 37.908 37.740 37.605
22 TC
82.255 75.536 69.536 63.537 57.537 52.737
SC
35.797 35.002 34.292 33.583 32.873 32.305
24 TC
91.090 83.367 76.471 69.576 62.680 57.163
SC
33.161 31.760 30.508 29.257 28.005 27.004
Model : M4RT250AR (Cooling Capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
66.597 62.666 59.156 55.645 52.135 49.327
SC
66.597 62.666 59.156 55.645 52.135 49.327
15 TC
71.095 66.400 62.208 58.016 53.824 50.470
SC
64.476 60.910 57.726 54.543 51.359 48.812
18 TC
83.361 76.584 70.532 64.480 58.429 53.587
SC
58.689 56.121 53.828 51.535 49.242 47.408
19.4 TC
89.086 81.336 74.416 67.497 60.578 55.042
SC
55.989 53.886 52.009 50.132 48.254 46.752
20 TC
91.539 83.648 76.603 69.557 62.512 56.876
SC
54.832 52.640 50.683 48.727 46.770 45.204
22 TC
99.717 91.355 83.890 76.425 68.959 62.987
SC
50.974 48.486 46.265 44.043 41.821 40.044
24 TC
107.894 99.063 91.178 83.292 75.407 69.099
SC
47.117 44.332 41.846 39.359 36.873 34.884
Model : M4RT300AR (Cooling Capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
83.246 78.171 73.639 69.108 64.577 60.951
SC
83.246 78.171 73.639 69.108 64.577 60.951
15 TC
88.836 82.773 77.359 71.945 66.532 62.201
SC
81.859 76.862 72.402 67.941 63.480 59.911
18 TC
104.082 95.323 87.503 79.683 71.863 65.607
SC
78.075 73.294 69.025 64.756 60.488 57.073
19.4 TC
111.197 101.180 92.237 83.294 74.351 67.197
SC
76.309 71.629 67.450 63.271 59.092 55.748
20 TC
114.246 104.075 94.994 85.914 76.833 69.568
SC
75.553 70.721 66.407 62.093 57.779 54.328
22 TC
124.409 113.725 104.185 94.645 85.105 77.473
SC
73.030 67.695 62.931 58.167 53.403 49.592
24 TC
134.573 123.374 113.375 103.376 93.377 85.378
SC
70.508 64.668 59.455 54.241 49.027 44.856
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C
M4RT080AR M4RT100AR M4RT150AR M4RT200AR M4RT250AR M4RT300AR
Bypass Factor
0.49 0.41 0.64 0.46 0.43 0.40