Heatpump Model (R22)
Model : MRT200AR (Cooling Capacity)
Indoor DB Indoor WB Ca
p
acit
y
Outdoor DB, ° C
° C ° C kW 19.4 25
30
35
40
44 46
26.7 13.9 TC
48.919 47.382 46.010 44.637 43.265 42.167 41.618
SC
48.919 47.382 46.010 44.637 43.265 42.167 41.618
15 TC
54.034 51.665 49.549 47.433 45.317 43.625 42.778
SC
47.393 46.162 45.063 43.964 42.865 41.985 41.545
17.2 TC
64.264 60.230 56.627 53.025 49.423 46.541 45.100
SC
44.341 43.722 43.169 42.617 42.064 41.622 41.401
18 TC
67.984 63.344 59.201 55.058 50.915 47.601 45.944
SC
43.231 42.835 42.481 42.127 41.773 41.490 41.348
19.4 TC
74.494 68.795 63.706 58.617 53.528 49.456 47.421
SC
41.289 41.282 41.276 41.270 41.264 41.259 41.256
20 TC
77.284 71.268 65.896 60.524 55.152 50.854 48.705
SC
40.456 40.258 40.081 39.904 39.726 39.585 39.514
22 TC
86.584 79.511 73.196 66.881 60.565 55.513 52.987
SC
37.682 36.845 36.097 35.350 34.603 34.005 33.706
24 TC
95.884 87.755 80.496 73.237 65.979 60.172 57.268
SC
34.907 33.431 32.114 30.797 29.479 28.425 27.898
Model : MRT250AR (Cooling Capacity)
Indoor DB Indoor WB Ca
p
acit
y
Outdoor DB, ° C
° C ° C kW 19.4 25
30
35
40
44 46
26.7 13.9 TC
67.956 63.945 60.363 56.781 53.199 50.334 48.901
SC
67.956 63.945 60.363 56.781 53.199 50.334 48.901
15 TC
72.546 67.755 63.477 59.200 54.922 51.500 49.789
SC
65.791 62.153 58.904 55.656 52.407 49.808 48.509
17.2 TC
81.725 75.375 69.706 64.037 58.368 53.833 51.565
SC
61.462 58.570 55.987 53.405 50.823 48.757 47.725
18 TC
85.063 78.146 71.971 65.796 59.621 54.681 52.211
SC
59.887 57.266 54.927 52.587 50.247 48.375 47.439
19.4 TC
90.904 82.996 75.935 68.875 61.814 56.165 53.341
SC
57.132 54.986 53.070 51.155 49.239 47.706 46.940
20 TC
93.407 85.355 78.166 70.977 63.788 58.036 55.161
SC
55.951 53.714 51.718 49.721 47.724 46.127 45.328
22 TC
101.752 93.220 85.602 77.984 70.367 64.273 61.226
SC
52.015 49.476 47.209 44.942 42.675 40.861 39.954
24 TC
110.096 101.084 93.038 84.992 76.946 70.509 67.290
SC
48.078 45.237 42.700 40.162 37.625 35.595 34.581
Model : MRT300AR (Cooling Capacity)
Indoor DB Indoor WB Ca
p
acit
y
Outdoor DB, ° C
° C ° C kW 19.4 25
30
35
40
44 46
26.7 13.9 TC
84.945 79.766 75.142 70.518 65.895 62.195 60.346
SC
84.945 79.766 75.142 70.518 65.895 62.195 60.346
15 TC
90.649 84.462 78.938 73.414 67.889 63.470 61.260
SC
83.529 78.431 73.879 69.327 64.775 61.134 59.313
17.2 TC
102.058 93.854 86.529 79.204 71.879 66.019 63.089
SC
80.698 75.761 71.353 66.944 62.536 59.010 57.246
18 TC
106.206 97.269 89.289 81.309 73.330 66.946 63.754
SC
79.668 74.790 70.434 66.078 61.722 58.237 56.495
19.4 TC
113.466 103.245 94.120 84.994 75.869 68.568 64.918
SC
77.867 73.091 68.826 64.562 60.297 56.886 55.180
20 TC
116.577 106.199 96.933 87.667 78.401 70.988 67.282
SC
77.094 72.164 67.762 63.360 58.958 55.436 53.675
22 TC
126.948 116.046
106.311
96.577 86.842 79.054 75.160
SC
74.521 69.076 64.215 59.354 54.493 50.604 48.660
24 TC
137.320 125.892
115.689
105.486 95.283 87.121 83.039
SC
71.947 65.988 60.668 55.348 50.028 45.772 43.644
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C
MRT080AR MRT100AR MRT150AR MRT200AR MRT250AR MRT300AR
Bypass Factor
0.49 0.40 0.64 0.46 0.43 0.40