Specifications

25
Heatpump Model (R22)
Model : MRT080AR (Cooling Capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 44 46
26.7 13.9 TC
19.484 18.887 18.354 17.820 17.287 16.860 16.647
SC
19.484 18.887 18.354 17.820 17.287 16.860 16.647
15 TC
21.468 20.563 19.754 18.946 18.137 17.490 17.167
SC
18.617 18.222 17.870 17.518 17.166 16.884 16.743
17.2 TC
25.437 23.914 22.555 21.196 19.837 18.750 18.206
SC
16.883 16.894 16.904 16.914 16.924 16.932 16.936
18 TC
26.880 25.133 23.574 22.014 20.455 19.208 18.584
SC
16.252 16.411 16.552 16.694 16.836 16.949 17.006
19.4 TC
29.405 27.266 25.356 23.447 21.537 20.009 19.245
SC
15.148 15.565 15.937 16.309 16.682 16.979 17.128
20 TC
30.487 28.221 26.198 24.174 22.151 20.532 19.723
SC
14.675 15.024 15.336 15.647 15.959 16.208 16.332
22 TC
34.095 31.404 29.002 26.600 24.198 22.276 21.315
SC
13.099 13.221 13.330 13.439 13.548 13.635 13.679
24 TC
37.702 34.588 31.807 29.026 26.245 24.020 22.907
SC
11.522 11.417 11.324 11.231 11.137 11.063 11.025
Model : MRT100AR (Cooling Capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 44 46
26.7 13.9 TC
28.042 26.520 25.160 23.800 22.441 21.353 20.809
SC
28.042 26.520 25.160 23.800 22.441 21.353 20.809
15 TC
28.179 27.003 25.952 24.902 23.851 23.011 22.591
SC
27.030 25.845 24.787 23.730 22.672 21.825 21.402
17.2 TC
28.453 27.969 27.537 27.105 26.673 26.328 26.155
SC
25.006 24.497 24.042 23.588 23.134 22.770 22.589
18 TC
28.552 28.320 28.113 27.906 27.699 27.534 27.451
SC
24.269 24.006 23.772 23.537 23.302 23.114 23.020
19.4 TC
28.726 28.935 29.122 29.308 29.495 29.644 29.719
SC
22.981 23.148 23.297 23.447 23.596 23.715 23.775
20 TC
28.801 28.964 29.110 29.256 29.402 29.519 29.577
SC
22.429 22.495 22.553 22.612 22.671 22.718 22.741
22 TC
29.050 29.062 29.072 29.083 29.093 29.102 29.106
SC
20.589 20.316 20.073 19.830 19.587 19.393 19.296
24 TC
29.298 29.159 29.034 28.909 28.784 28.684 28.634
SC
18.748 18.138 17.593 17.048 16.504 16.068 15.850
Model : MRT150AR (Cooling Capacity)
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 44 46
26.7 13.9 TC
42.995 40.515 38.300 36.086 33.871 32.099 31.213
SC
40.437 38.495 36.762 35.028 33.294 31.907 31.213
15 TC
43.804 41.599 39.630 37.661 35.692 34.117 33.329
SC
38.040 36.855 35.797 34.738 33.680 32.833 32.410
17.2 TC
45.421 43.766 42.289 40.812 39.334 38.152 37.562
SC
33.246 33.574 33.867 34.159 34.452 34.686 34.803
18 TC
46.009 44.555 43.256 41.957 40.659 39.620 39.101
SC
31.503 32.381 33.165 33.949 34.733 35.360 35.673
19.4 TC
47.038 45.934 44.948 43.962 42.977 42.188 41.794
SC
28.452 30.293 31.937 33.580 35.224 36.539 37.196
20 TC
47.479 46.314 45.274 44.233 43.193 42.361 41.945
SC
27.145 28.863 30.397 31.931 33.465 34.692 35.306
22 TC
48.949 47.581 46.359 45.137 43.915 42.937 42.448
SC
22.786 24.095 25.264 26.432 27.601 28.536 29.003
24 TC
50.420 48.847 47.444 46.040 44.636 43.513 42.951
SC
18.428 19.327 20.130 20.934 21.737 22.379 22.700
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C