Specifications
24
Cooling Only (R407C)
Model : M4RT250A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
63.322 60.067 57.161 54.254 51.348 47.860
SC
63.322 60.067 57.161 54.254 51.348 47.860
15 TC
67.466 63.668 60.277 56.885 53.494 49.424
SC
60.977 58.170 55.663 53.157 50.650 47.643
18 TC
78.769 73.489 68.775 64.061 59.347 53.690
SC
54.582 52.996 51.580 50.164 48.748 47.048
19.4 TC
84.043 78.072 72.741 67.409 62.078 55.680
SC
51.598 50.582 49.675 48.767 47.860 46.771
20 TC
86.304 80.136 74.629 69.123 63.616 57.008
SC
50.319 49.193 48.188 47.182 46.177 44.971
22 TC
93.839 87.017 80.925 74.834 68.743 61.433
SC
46.056 44.564 43.232 41.899 40.567 38.969
24 TC
101.374 93.897 87.221 80.545 73.870 65.859
SC
41.793 39.935 38.276 36.617 34.958 32.967
Model : M4RT300A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
84.803 79.304 74.394 69.484 64.573 58.681
SC
84.803 79.304 74.394 69.484 64.573 58.681
15 TC
87.420 81.927 77.022 72.117 67.212 61.326
SC
81.241 76.443 72.159 67.875 63.591 58.450
18 TC
94.557 89.079 84.189 79.298 74.408 68.539
SC
71.525 68.639 66.063 63.487 60.910 57.819
19.4 TC
97.887 92.417 87.533 82.649 77.766 71.905
SC
66.991 64.998 63.218 61.439 59.659 57.524
20 TC
99.314 93.787 88.851 83.916 78.981 73.059
SC
65.048 63.025 61.218 59.412 57.606 55.438
22 TC
104.072 98.352 93.245 88.139 83.032 76.904
SC
58.570 56.447 54.552 52.656 50.760 48.485
24 TC
108.830 102.918 97.639 92.361 87.083 80.749
SC
52.093 49.870 47.885 45.900 43.915 41.533
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C
M4RT060A M4RT080A M4RT100A M4RT120A M4RT150A M4RT200A M4RT250A M4RT300A
Bypass Factor
0.47 0.45 0.51 0.40 0.40 0.42 0.46 0.38