Specifications
22
Cooling Only (R407C)
Model : M4RT060A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
16.120 15.311 14.588 13.866 13.144 12.277
SC
15.488 14.812 14.208 13.605 13.001 12.277
15 TC
17.435 16.400 15.475 14.551 13.627 12.518
SC
15.256 14.543 13.907 13.271 12.635 11.871
18 TC
21.021 19.370 17.895 16.420 14.945 13.175
SC
14.625 13.812 13.086 12.360 11.634 10.763
19.4 TC
22.695 20.756 19.024 17.292 15.560 13.482
SC
14.330 13.470 12.703 11.935 11.167 10.246
20 TC
23.413 21.416 19.633 17.850 16.067 13.927
SC
14.204 13.311 12.513 11.716 10.919 9.962
22 TC
25.804 23.616 21.662 19.709 17.755 15.411
SC
13.783 12.779 11.883 10.987 10.090 9.015
24 TC
28.195 25.816 23.692 21.567 19.443 16.894
SC
13.362 12.247 11.252 10.257 9.262 8.068
Model : M4RT080A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
17.209 16.740 16.322 15.903 15.485 14.982
SC
17.114 16.665 16.264 15.864 15.463 14.982
15 TC
18.593 18.001 17.472 16.943 16.414 15.779
SC
16.258 15.933 15.644 15.354 15.065 14.717
18 TC
22.370 21.440 20.609 19.779 18.948 17.952
SC
13.924 13.939 13.952 13.965 13.977 13.993
19.4 TC
24.132 23.044 22.073 21.102 20.131 18.965
SC
12.835 13.008 13.162 13.316 13.470 13.655
20 TC
24.887 23.686 22.613 21.541 20.468 19.181
SC
12.369 12.512 12.639 12.767 12.895 13.048
22 TC
27.405 25.825 24.414 23.003 21.592 19.899
SC
10.813 10.858 10.898 10.937 10.977 11.025
24 TC
29.923 27.963 26.214 24.465 22.716 20.617
SC
9.257 9.204 9.156 9.107 9.059 9.002
Model : M4RT100A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46
26.7 13.9 TC
25.620 24.388 23.288 22.188 21.088 19.768
SC
25.620 24.388 23.288 22.188 21.088 19.768
15 TC
27.916 26.266 24.793 23.319 21.846 20.077
SC
25.283 23.930 22.721 21.513 20.305 18.855
18 TC
34.180 31.388 28.896 26.404 23.911 20.920
SC
24.364 22.680 21.176 19.672 18.168 16.363
19.4 TC
37.103 33.779 30.811 27.843 24.875 21.314
SC
23.935 22.097 20.455 18.813 17.171 15.201
20 TC
38.355 34.929 31.870 28.811 25.752 22.082
SC
23.752 21.883 20.215 18.547 16.879 14.877
22 TC
42.531 38.765 35.402 32.040 28.677 24.642
SC
23.139 21.173 19.417 17.660 15.904 13.797
24 TC
46.707 42.601 38.934 35.268 31.602 27.203
SC
22.527 20.462 18.618 16.774 14.930 12.718
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C