Specifications
21
Cooling Only (R22)
Model : MRT250A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
68.828 65.290 62.131 58.972 55.813 52.022 49.495 48.231 46.968
SC
68.828 65.290 62.131 58.972 55.813 52.022 49.495 48.231 46.968
15 TC
73.333 69.204 65.518 61.832 58.146 53.722 50.773 49.299 47.824
SC
66.280 63.228 60.504 57.779 55.055 51.785 49.606 48.516 47.426
18 TC
85.618 79.879 74.755 69.631 64.507 58.358 54.259 52.209 50.160
SC
59.329 57.605 56.065 54.526 52.987 51.140 49.908 49.292 48.677
19.4 TC
91.351 84.861 79.066 73.271 67.476 60.522 55.886 53.568 51.250
SC
56.085 54.980 53.994 53.008 52.022 50.838 50.049 49.655 49.260
20 TC
93.808 87.105 81.119 75.133 69.148 61.965 57.176 54.782 52.388
SC
54.695 53.471 52.378 51.285 50.192 48.881 48.007 47.570 47.133
22 TC
101.999 94.583 87.962 81.341 74.720 66.775 61.478 58.830 56.182
SC
50.061 48.439 46.991 45.543 44.095 42.357 41.199 40.620 40.040
24 TC
110.189 102.062 94.806 87.549 80.293 71.586 65.781 62.878 59.976
SC
45.427 43.407 41.604 39.801 37.997 35.833 34.391 33.669 32.948
Model : MRT300A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
90.216 84.366 79.142 73.919 68.695 62.427 58.248 56.158 54.069
SC
90.216 84.366 79.142 73.919 68.695 62.427 58.248 56.158 54.069
15 TC
93.000 87.156 81.938 76.720 71.502 65.240 61.066 58.979 56.892
SC
86.426 81.322 76.765 72.207 67.650 62.181 58.535 56.712 54.889
18 TC
100.592 94.765 89.562 84.360 79.157 72.914 68.752 66.671 64.589
SC
76.090 73.021 70.280 67.539 64.798 61.509 59.316 58.220 57.124
19.4 TC
104.135 98.316 93.121 87.925 82.729 76.495 72.338 70.260 68.182
SC
71.267 69.147 67.254 65.360 63.467 61.196 59.681 58.924 58.167
20 TC
105.654 99.773 94.523 89.273 84.022 77.722 73.522 71.421 69.321
SC
69.200 67.047 65.126 63.204 61.283 58.977 57.440 56.671 55.902
22 TC
110.715 104.630 99.197 93.764 88.332 81.812 77.466 75.293 73.120
SC
62.309 60.050 58.034 56.017 54.000 51.580 49.967 49.160 48.354
24 TC
115.776 109.487 103.872 98.256 92.641 85.903 81.410 79.164 76.918
SC
55.418 53.053 50.941 48.829 46.718 44.184 42.494 41.650 40.805
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C
MRT060A MRT080A MRT100A MRT120A MRT150A MRT200A MRT250A MRT300A
Bypass Factor
0.47 0.45 0.51 0.40 0.40 0.42 0.46 0.38