Specifications

20
Cooling Only (R22)
Model : MRT120A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
33.116 31.226 29.538 27.851 26.163 24.138 22.788 22.113 21.438
SC
33.116 31.226 29.538 27.851 26.163 24.138 22.788 22.113 21.438
15 TC
36.035 33.539 31.309 29.080 26.851 24.176 23.487 22.666 21.846
SC
32.530 30.607 28.891 27.174 25.457 23.397 21.924 21.231 20.538
18 TC
43.998 39.846 36.140 32.433 28.726 24.278 25.391 24.175 22.959
SC
30.933 28.921 27.125 25.328 23.532 21.377 19.568 18.825 18.083
19.4 TC
47.714 42.790 38.394 33.998 29.601 24.326 27.971 24.879 23.478
SC
30.187 28.134 26.301 24.467 22.634 20.434 18.469 17.703 16.937
20 TC
49.306 44.292 39.814 35.336 30.859 25.485 26.660 25.180 23.700
SC
29.868 27.775 25.906 24.037 22.168 19.926 17.997 17.222 16.446
22 TC
54.615 49.296 44.547 39.798 35.049 29.351 27.930 26.186 24.442
SC
28.803 26.578 24.591 22.604 20.617 18.233 16.427 15.618 14.809
24 TC
59.923 54.301 49.280 44.260 39.240 33.216 29.200 27.191 25.183
SC
27.738 25.381 23.276 21.171 19.066 16.540 14.856 14.014 13.172
Model : MRT150A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
47.461 44.040 40.986 37.932 34.878 31.213 28.770 27.549 26.327
SC
47.461 44.040 40.986 37.932 34.878 31.213 28.770 27.549 26.327
15 TC
47.984 44.809 41.973 39.138 36.303 32.901 30.633 29.499 28.365
SC
43.738 41.040 38.632 36.223 33.815 30.924 28.997 28.034 27.071
18 TC
49.411 46.904 44.666 42.427 40.189 37.503 35.713 34.818 33.922
SC
33.585 32.859 32.211 31.562 30.914 30.136 29.617 29.358 29.098
19.4 TC
50.077 47.882 45.922 43.962 42.003 39.651 38.084 37.300 36.516
SC
28.847 29.041 29.214 29.387 29.560 29.768 29.906 29.976 30.045
20 TC
50.362 48.198 46.265 44.333 42.401 40.082 38.536 37.763 36.990
SC
26.817 27.166 27.478 27.790 28.102 28.476 28.726 28.851 28.975
22 TC
51.313 49.251 47.409 45.568 43.726 41.517 40.043 39.307 38.570
SC
20.048 20.916 21.691 22.466 23.241 24.171 24.791 25.101 25.411
24 TC
52.265 50.304 48.553 46.803 45.052 42.951 41.551 40.851 40.150
SC
13.280 14.666 15.904 17.142 18.380 19.866 20.856 21.351 21.846
Model : MRT200A
Indoor DB Indoor WB Capacity Outdoor DB, ° C
° C ° C kW 19.4 25 30 35 40 46 50 52 54
26.7 13.9 TC
55.510 52.585 49.974 47.363 44.751 41.618 39.529 38.484 37.440
SC
53.129 50.705 48.542 46.378 44.214 41.618 39.529 38.484 37.440
15 TC
57.029 54.367 51.990 49.613 47.237 44.385 41.261 40.231 39.200
SC
50.544 48.593 46.852 45.111 43.369 41.279 38.555 37.815 37.076
18 TC
61.172 59.226 57.489 55.752 54.015 51.930 45.986 44.993 44.001
SC
43.495 42.834 42.244 41.654 41.064 40.356 35.897 35.989 36.083
19.4 TC
63.106 61.494 60.055 58.617 57.178 55.451 52.387 47.216 46.241
SC
40.206 40.147 40.094 40.041 39.988 39.925 34.657 35.138 35.619
20 TC
63.934 62.198 60.648 59.098 57.548 55.688 49.136 48.169 47.201
SC
38.796 38.681 38.578 38.475 38.372 38.248 34.125 34.773 35.420
22 TC
66.696 64.545 62.625 60.704 58.783 56.478 52.286 51.344 50.402
SC
34.097 33.794 33.523 33.253 32.982 32.658 32.354 33.556 34.758
24 TC
69.458 66.892 64.601 62.309 60.018 57.268 55.435 54.519 53.602
SC
29.397 28.907 28.469 28.031 27.593 27.068 30.582 32.339 34.096
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the formula below :
Sensible capacity (@EDB) (kW) = Sensible capacity (@26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, EDB = Entering dry bulb temperature, °C