MRT - 2004 Rooftop Packaged Air Conditioners Models: MRT MRT MRT MRT MRT MRT MRT MRT 080A/AR 100A/AR 150A/AR 200A/AR 250A/AR 300A/AR 060A 120A M4RT M4RT M4RT M4RT M4RT M4RT 080A/AR 100A/AR 150A/AR 200A/AR 060A 120A
Contents Safety precautions ................................................................................................. 1 Nomenclature ......................................................................................................... 2 Features .................................................................................................................. 3 Specifications......................................................................................................... 4 Noise level ...
Safety Precautions Before installing the air conditioner unit, please read the following safety precautions carefully. Warning • • • • • • • Installation and maintenance should be performed by qualified persons who are familiar with local code and regulation, and experienced with this type of appliance. All field wiring must be installed in accordance with the national wiring regulation.
Nomenclature M 4 RT 60 A R Model Type – R: Heatpump Omitted if Cooling Series – A: A series Capacity – 60: 60,000 Btu/h Model Name – RT: Rooftop Type of Refrigerant System - 4: R407C system Omitted if R22 system Brand - M : MCQUAY 2
Features High Efficiency The McQuay rooftop unit is design with high efficiency and reliability scroll compressor. Package Unit The design of one single unit configuration, all refrigerant work at site can be eliminated. This will ensure expedited installation time and minimise installation labour involve. The refrigerant is factory charged to ensure clean and efficient operation.
Specifications Cooling Model (50Hz – R22) MODEL TOTAL COOLING CAPACITY SENSIBLE COOLING CAPACITY RATED TOTAL POWER INPUT RATED RUNNING CURRENT POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER FAN FAN MOTOR NO OF FAN MOTOR / OUTPUT AIR FLOW EXTERNAL STATIC PRESSURE kcal/h kW Btu/h kcal/h kW Btu/h W A V/Ph/Hz % CONTROL DIMENSION NET WEIGHT AIR FILTER POWER SOURCE COMPRESSOR NO
Cooling Model (50Hz – R22) MODEL TOTAL COOLING CAPACITY SENSIBLE COOLING CAPACITY RATED TOTAL POWER CONSUMPTION RATED RUNNING CURRENT POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER kcal/h kW Btu/h kcal/h kW Btu/h W A V/Ph/Hz % kg AIR FLOW EXTERNAL STATIC PRESSURE ROOM TEMPERATURE CONTROL OPERATION DRAIN CONNECTION HEIGHT DIMENSION WIDTH DEPTH NET WEIGHT AIR FILTER POWER SO
Cooling Model (50Hz – R22) MODEL OUTDOOR 35OC DB TOTAL COOLING CAPACITY OUTDOOR 46OC DB OUTDOOR 35OC DB SENSIBLE COOLING CAPACITY OUTDOOR 46OC DB RATED TOTAL POWER CONSUMPTION RATED RUNNING CURRENT POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS INSULATION FAN FAN MOTOR NO OF FAN MOTOR / OUTPUT AIR FLOW EXTERNAL STATIC PRESSURE kcal/h kW Btu/h kcal/h kW Btu/h kcal/h kW Btu/h kcal/h kW
Cooling Model (50Hz – R407C) MODEL TOTAL COOLING CAPACITY SENSIBLE COOLING CAPACITY RATED TOTAL POWER INPUT RATED RUNNING CURRENT POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER FAN FAN MOTOR NO OF FAN MOTOR / OUTPUT AIR FLOW EXTERNAL STATIC PRESSURE kcal/h kW Btu/h kcal/h kW Btu/h W A V/Ph/Hz % CONTROL DIMENSION NET WEIGHT AIR FILTER POWER SOURCE COMPRESSOR NO / TYPE RATED
Cooling Model (50Hz – R407C) M4RT080A M4RT100A M4RT150A M4RT200A kcal/h kW Btu/h kcal/h kW Btu/h W A V/Ph/Hz % 18144 21.1 72000 13431 12.7 53300 8700 16.3 23940 27.8 95000 18194 21.2 72200 11600 20.2 35279 41.0 140000 25754 30.0 102200 17200 32.1 47879 55.7 190000 33994 39.5 134900 25100 43.8 kg 4.
Cooling Model (50Hz – R407C) MODEL OUTDOOR 35OC DB TOTAL COOLING CAPACITY OUTDOOR 46OC DB OUTDOOR 35OC DB SENSIBLE COOLING CAPACITY OUTDOOR 46OC DB RATED TOTAL POWER CONSUMPTION RATED RUNNING CURRENT POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER FAN FAN MOTOR NO OF FAN MOTOR / OUTPUT AIR FLOW EXTERNAL STATIC PRESSURE M4RT250A M4RT300A kcal/h kW Btu/h kcal/h kW Btu/h kcal/h
Heatpump Model (50Hz – R22) MODEL TOTAL COOLING CAPACITY SENSIBLE COOLING CAPACITY TOTAL HEATING CAPACITY RATED TOTAL POWER CONSUMPTION (COOLING) RATED TOTAL POWER CONSUMPTION (HEATING) RATED RUNNING CURRENT (COOLING) RATED RUNNING CURRENT (HEATING) POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER kcal/h kW Btu/h kcal/h kW Btu/h kcal/h kW Btu/h W W A A V/Ph/Hz % kg AIR FLOW
Cooling Model (50Hz – R22) MODEL O OUTDOOR 35 C DB TOTAL COOLING CAPACITY O OUTDOOR 46 C DB O OUTDOOR 35 C DB SENSIBLE COOLING CAPACITY O OUTDOOR 46 C DB TOTAL HEATING CAPACITY RATED TOTAL POWER CONSUMPTION (COOLING) RATED TOTAL POWER CONSUMPTION (HEATING) RATED RUNNING CURRENT (COOLING) RATED RUNNING CURRENT (HEATING) POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS INSULATION FAN
Heatpump Model (50Hz – R407C) MODEL TOTAL COOLING CAPACITY SENSIBLE COOLING CAPACITY TOTAL HEATING CAPACITY RATED TOTAL POWER CONSUMPTION (COOLING) RATED TOTAL POWER CONSUMPTION (HEATING) RATED RUNNING CURRENT (COOLING) RATED RUNNING CURRENT (HEATING) POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER kcal/h kW Btu/h kcal/h kW Btu/h kcal/h kW Btu/h W W A A V/Ph/Hz % kg AIR FLO
Heatpump Model (50Hz – R407C) MODEL OUTDOOR 35OC DB TOTAL COOLING CAPACITY OUTDOOR 46OC DB OUTDOOR 35OC DB SENSIBLE COOLING CAPACITY OUTDOOR 46OC DB TOTAL HEATING CAPACITY RATED TOTAL POWER CONSUMPTION (COOLING) RATED TOTAL POWER CONSUMPTION (HEATING) RATED RUNNING CURRENT (COOLING) RATED RUNNING CURRENT (HEATING) POWER SOURCE CAPACITY STEPS REFRIGERANT REFRIGERANT CHARGE REFRIGERANT CONTROL EVAPORATOR MATERIAL FIN THICKNESS ROW / FIN PER INCH FACE AREA MATERIAL TUBE WALL THICKNESS DIAMETER FAN FAN MOTOR NO
Noise Level Model M(4)RT060A M(4)RT080A/AR M(4)RT100A/AR M(4)RT120A M(4)RT150A/AR M(4)RT200A/AR M(4)RT250A/AR M(4)RT300A/AR 1/1 Octave Sound Pressure Level (dB, ref 20µ Pa) 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz 67 61 59 60 55 49 42 51 56 61 62 55 50 38 52 58 61 60 57 52 40 68 64 62 65 60 53 45 58 59 65 67 61 54 42 57 60 63 66 61 53 41 76 72 70 71 65 55 46 77 72 71 72 65 55 46 Note: 1.
M(4)RT060A NC Curves (415V, 50Hz) 80 Sound pressure level (dB, ref 20µPa) 70 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) M(4)RT080A/AR NC Curves (415V, 50Hz) 80 Sound pressure level (dB, ref 20µPa) 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 Octave-band frequency (Hz) 15 4000 8000
M(4)RT100A/AR NC Curves (415V, 50Hz) 80 Sound pressure level (dB, ref 20µPa) 70 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) M(4)RT120A NC Curves (415V, 50Hz) 80 Sound pressure level (dB, ref 20µPa) 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 Octave-band frequency (Hz) 16 4000 8000
M(4)RT150A/AR NC Curves (415V, 50Hz) 90 Sound pressure level (dB, ref 20µPa) 80 NC-70 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) M(4)RT 200A/AR NC Curves (415V, 50Hz) 80 Sound pressure level (dB, ref 20µPa) 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 Octave-band frequency(Hz) 17 4000 8000
M(4)RT 250A/AR NC Curves 90 Sound pressure level (dB, ref 20µPa) 80 NC-70 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 4000 8000 Octave-band frequency (Hz) M(4)RT 300A/AR NC Curves (415V, 50Hz) 90 Sound pressure level (dB, ref 20µPa) 80 NC-70 70 NC-65 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 NC-25 20 NC-20 10 0 125 250 500 1000 2000 Octave-band frequency (Hz) 18 4000 8000
Performance Table Cooling Only (R22) Model : MRT060A Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 16.120 15.488 17.435 15.256 21.021 14.625 22.695 14.330 23.413 14.204 25.804 13.783 28.195 13.362 25 15.311 14.812 16.400 14.543 19.370 13.812 20.756 13.470 21.416 13.311 23.616 12.779 25.816 12.247 30 14.588 14.208 15.475 13.907 17.895 13.086 19.024 12.703 19.633 12.513 21.662 11.883 23.692 11.252 Outdoor DB, ° C 35 40 46 13.866 13.
Cooling Only (R22) Model : MRT120A Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 33.116 33.116 36.035 32.530 43.998 30.933 47.714 30.187 49.306 29.868 54.615 28.803 59.923 27.738 25 31.226 31.226 33.539 30.607 39.846 28.921 42.790 28.134 44.292 27.775 49.296 26.578 54.301 25.381 30 29.538 29.538 31.309 28.891 36.140 27.125 38.394 26.301 39.814 25.906 44.547 24.591 49.280 23.276 Outdoor DB, ° C 35 40 46 27.851 26.163 24.138 27.851 26.
Cooling Only (R22) Model : MRT250A Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 25 68.828 65.290 68.828 65.290 73.333 69.204 66.280 63.228 85.618 79.879 59.329 57.605 91.351 84.861 56.085 54.980 93.808 87.105 54.695 53.471 101.999 94.583 50.061 48.439 110.189 102.062 45.427 43.407 30 62.131 62.131 65.518 60.504 74.755 56.065 79.066 53.994 81.119 52.378 87.962 46.991 94.806 41.604 Outdoor DB, ° C 35 40 46 58.972 55.813 52.022 58.
Cooling Only (R407C) Model : M4RT060A Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 16.120 15.488 17.435 15.256 21.021 14.625 22.695 14.330 23.413 14.204 25.804 13.783 28.195 13.362 25 15.311 14.812 16.400 14.543 19.370 13.812 20.756 13.470 21.416 13.311 23.616 12.779 25.816 12.247 Outdoor DB, ° C 30 35 14.588 13.866 14.208 13.605 15.475 14.551 13.907 13.271 17.895 16.420 13.086 12.360 19.024 17.292 12.703 11.935 19.633 17.850 12.
Cooling Only (R407C) Model : M4RT120A Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 31.460 31.460 34.234 30.904 41.798 29.386 45.328 28.678 46.841 28.374 51.884 27.363 56.927 26.351 25 29.664 29.664 31.862 29.077 37.854 27.475 40.651 26.727 42.077 26.386 46.831 25.249 51.586 24.111 Outdoor DB, ° C 30 35 28.061 26.458 28.061 26.458 29.744 27.626 27.446 25.815 34.333 30.811 25.768 24.062 36.474 32.298 24.986 23.244 37.823 33.569 24.
Cooling Only (R407C) Model : M4RT250A Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 63.322 63.322 67.466 60.977 78.769 54.582 84.043 51.598 86.304 50.319 93.839 46.056 101.374 41.793 25 60.067 60.067 63.668 58.170 73.489 52.996 78.072 50.582 80.136 49.193 87.017 44.564 93.897 39.935 Outdoor DB, ° C 30 35 57.161 54.254 57.161 54.254 60.277 56.885 55.663 53.157 68.775 64.061 51.580 50.164 72.741 67.409 49.675 48.767 74.629 69.123 48.
Heatpump Model (R22) Model : MRT080AR (Cooling Capacity) Indoor DB °C 26.7 Indoor WB °C 13.9 15 17.2 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 19.484 19.484 21.468 18.617 25.437 16.883 26.880 16.252 29.405 15.148 30.487 14.675 34.095 13.099 37.702 11.522 25 18.887 18.887 20.563 18.222 23.914 16.894 25.133 16.411 27.266 15.565 28.221 15.024 31.404 13.221 34.588 11.417 30 18.354 18.354 19.754 17.870 22.555 16.904 23.574 16.552 25.356 15.937 26.198 15.336 29.002 13.
Heatpump Model (R22) Model : MRT200AR (Cooling Capacity) Indoor DB °C 26.7 Indoor WB °C 13.9 15 17.2 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 48.919 48.919 54.034 47.393 64.264 44.341 67.984 43.231 74.494 41.289 77.284 40.456 86.584 37.682 95.884 34.907 25 47.382 47.382 51.665 46.162 60.230 43.722 63.344 42.835 68.795 41.282 71.268 40.258 79.511 36.845 87.755 33.431 30 46.010 46.010 49.549 45.063 56.627 43.169 59.201 42.481 63.706 41.276 65.896 40.081 73.196 36.
Heatpump Model (R22) Model : M4RT080AR (Cooling Capacity) Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 17.536 17.536 19.321 16.755 24.192 14.627 26.464 13.633 27.438 13.208 30.685 11.789 33.932 10.370 25 16.998 16.998 18.506 16.400 22.620 14.770 24.539 14.009 25.399 13.522 28.264 11.899 31.129 10.276 Outdoor DB, ° C 30 35 16.518 16.038 16.518 16.038 17.779 17.051 16.083 15.766 21.216 19.813 14.897 15.025 22.821 21.102 14.344 14.
Heatpump Model (R22) Model : M4RT200AR (Cooling Capacity) Indoor DB °C 26.7 Indoor WB °C 13.9 15 18 19.4 20 22 24 Capacity kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC 19.4 46.473 46.473 51.333 45.024 64.585 41.070 70.770 39.224 73.420 38.434 82.255 35.797 91.090 33.161 25 45.013 45.013 49.081 43.854 60.177 40.693 65.355 39.218 67.704 38.245 75.536 35.002 83.367 31.760 Outdoor DB, ° C 30 35 43.709 42.405 43.709 42.405 47.071 45.061 42.810 41.766 56.241 52.305 40.357 40.021 60.520 55.686 39.212 39.
Heatpump Model (R22) Model : MRT080AR (Heating Capacity) Capacity WB°C -11.0 kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC -9.0 -5.0 6.0 12.0 15.0 18.3 Indoor DB°C 15.0 17.0 19.0 21.0 24.0 26.7 12.672 12.672 13.731 13.731 15.849 15.849 21.674 21.674 24.852 24.852 26.440 26.440 28.188 28.188 12.558 12.558 13.601 13.601 15.707 15.707 22.128 22.128 24.630 24.630 26.205 26.205 27.937 27.937 12.444 12.444 13.470 13.470 15.565 15.565 22.582 22.582 24.408 24.408 25.969 25.969 27.685 27.685 12.330 12.
Heatpump Model (R22) Model : MRT200AR (Heating Capacity) Capacity WB°C -11.0 kW TC SC TC SC TC SC TC SC TC SC TC SC TC SC -9.0 -5.0 6.0 12.0 15.0 18.3 Indoor DB°C 15.0 17.0 19.0 21.0 24.0 26.7 32.966 32.966 36.590 36.590 43.837 43.837 63.766 63.766 74.637 74.637 80.072 80.072 86.051 86.051 32.669 32.669 35.960 35.960 43.444 43.444 62.831 62.831 73.971 73.971 79.358 79.358 85.284 85.284 32.373 32.373 35.331 35.331 43.051 43.051 61.896 61.896 73.305 73.305 78.644 78.644 84.517 84.517 32.076 32.
Heatpump Model (R407C) Model : M4RT080AR (Heating Capacity) Indoor DB Indoor WB Capacity °C °C kW -11.0°C -9.0°C -5.0°C 6.0°C 12.0°C 15.0°C 18.3°C 26.7 15.0°C TC 12.414 13.452 15.527 21.233 24.346 25.902 27.614 SC 12.414 13.452 15.527 21.233 24.346 25.902 27.614 TC 12.302 13.324 15.388 21.678 24.129 25.671 27.368 17.0°C 19.0°C 21.0°C 24.0°C 26.7°C Outdoor DB, ° C SC 12.302 13.324 15.388 21.678 24.129 25.671 27.368 TC 12.191 13.196 15.248 22.123 23.
Heatpump Model (R407C) Model : M4RT200AR (Heating Capacity) Indoor DB Indoor WB Capacity °C °C kW -11.0°C -9.0°C -5.0°C 6.0°C 12.0°C 15.0°C 18.3°C 26.7 15.0°C TC 36.453 40.460 48.473 70.511 82.531 88.541 95.153 SC 36.453 40.460 48.473 70.511 82.531 88.541 95.153 TC 36.125 39.764 48.039 69.477 81.795 87.752 94.305 17.0°C 19.0°C 21.0°C 24.0°C 26.7°C Outdoor DB, ° C SC 36.125 39.764 48.039 69.477 81.795 87.752 94.305 TC 35.797 39.067 47.604 68.443 81.
Electrical Data Power Input Table Cooling Only (R22) Model: MRT060A Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Model: MRT150A Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Cooling Only (R407C) Model: M4RT060A Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Model: M4RT150A Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Heatpump Model (R22) Cooling Capacity Model: MRT080AR Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Heatpump Model (R22) Cooling Capacity Model: MRT250AR Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Heatpump Model (R407C) Cooling Capacity Model: M4RT150AR Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Heatpump Model (R22) Heating Capacity Model: MRT080AR Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Heatpump Model (R22) Heating Capacity Model: MRT250AR Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Heatpump Model (R407C) Heating Capacity Model: M4RT150AR Indoor WB °C 13.9 15 16.7 18 19.4 20 22 22.2 24 19.
Operating Range Ensure the operating temperature is in allowable range. Cooling (R22) Cooling (R407C) Outdoor temp. (°C DB) Outdoor temp. (°CWB) 54 50 40 30 20 10 50 46 40 30 20 10 0 0 -5 -5 -10 10 15 20 24 25 -10 10 30 15 20 24 25 30 Indoor temp. (°C WB) Indoor temp. (°CWB) Heat pump (R22 & R407C) Heating Cooling 20 Outdoor temp. (°C DB) Outdoor temp. (°CWB) 15 10 5 0 -5 50 46 40 30 20 10 0 -10 -5 -10 10 -15 15 20 24 25 Indoor temp.
Drive Package Selection Table M(4)RT060A/AR Total SP (Pa) Std. CMM Fan Speed Pulley Size (Motor) 150 Pulley Size (Fan Side) Belt Size Motor Fan Speed Pulley Size (Motor) 200 Pulley Size (Fan Side) Belt Size Motor Fan Speed Pulley Size (Motor) 250 M(4)RT080A/AR Std.
M(4)RT100A/AR, 120A Std. M(4)RT150A/AR Air flow Total SP (Pa) Fan speed Pulley size (Motor side) 250 Pulley size (Fan side) Belt size Motor Fan speed Pulley size (Motor side) 350 Pulley size (Fan side) Belt size Motor Fan speed Pulley size (Motor side) 450 Pulley size (Fan side) Belt size Motor Fan speed Pulley size (Motor side) 550 Pulley size (Fan side) Belt size Motor Air flow 300 400 500 600 100 1660 1088 114.3 4.5 152.4 6 B31 1.5 1208 127 5 152.4 6 B32 1.5 1450 127 5 127 5 B30 2.
M(4)RT200A/AR Air flow Total SP (Pa) Std.
M(4)RT300A/AR Std.
Pulley outside dimensions are shown below : (Unit : mm) (1) Shape of belt groove 1.1 Shape of Nominal a V-belt Dia. ∅P.C (°) B Lo K Ko e W f r2 r3 V-belt thickness (Reference) 0.5~1.0 1~2 11 r1 Over 125 Under 160 34 15.86 Over 160 Under 200 36 16.07 12.5 5.5 9.5 19.0 12.5 0.2~0.5 Over 200 38 16.29 Sectional plan of V-belt 1.2 Taper lock type (MRT250/300A/AR) Section Sheave dia. dd Groove angle β Wd bmin hmin SPZ 71 – 80 > 80 34° 38° 8.5 2.0 9.0 e f 12 ± 0.
Fan Performance Curve M(4)RT060A/AR M(4)RT080A/AR 49
M(4)RT100A/AR, 120A M(4)RT150A/AR 50
M(4)RT200A/AR M(4)RT250A/AR 51
M(4)RT300A/AR 52
Outlines And Dimensions M(4)RT060A MRT080/100A/AR, M4RT080/100A (side flow) 53
MRT080/100A/AR, M4RT080/100A (down flow) M(4)RT120A (side flow) 54
M(4)RT120A (down flow) MRT150/200A/AR, M4RT150/200A (side flow) 55
MRT150/200A/AR, M4RT150/200A (down flow) MRT250/300A/AR 56
Schematic Diagram Model : MRT080/100/150/200A (R22) M4RT080/100/150/200A (R407C) Model : MRT080/100/150/200AR (R22) 57
Model : MRT060/120A, MRT250/300A (R22) M4RT060/120A, M4RT250/300A (R407C) Model : MRT250/300AR (R22) M4RT080/100/150/200/250/300AR (R407C) 58
Wiring Diagrams ART080A M(4)RT060A ARRANGEMENT Symbol Caution, 1. To protect each Fan motor and Compressor from abnormal current, Over current relays <51C>, <51F> are installed. Therefore, do not change factory set value of Over current relays. Note: 1. The dotted lines show field wiring. 2. The figure in the parentheses shows field supply parts. 3. Color of earth is yellow and green twisting. 4. If the power supply is 380AV, change the “C03” connector with silver color tape to red color tape. 5.
MRT080A MRT100A (MECHANICAL CONTROL) Symbol Name Symbol Name MC Compressor motor 63H High-pressure switch MF1 Fan motor (indoor) FZ Auxiliary relay (fan) MF2 Fan motor (outdoor) CZ Auxiliary relay (compressor) 52C Contactor (compressor) 30CZ,30FZ Auxiliary relay (check) 52F Contactor (fan I/D) Switch (on) TB1,2 Terminal block <23WA> Thermostat (room temp.) F1, F2 Fuse (3.
MRT080AR MRT100AR (STANDARD : MECHANICAL CONTROL) Symbol Name Symbol Name Symbol Name MC Compressor motor CR1,2 Surge killer CH Crankcase heater MF1 Fan motor (indoor) 63H High-pressure switch T1,2 Timer (defrost) MF2 Fan motor (outdoor) FZ Auxiliary relay (fan) 21S4 4-way valve 52C Contactor (compressor) CZ Auxiliary relay (compressor) C03,04,05,11-15 Connector 52F Contactor (fan I/D) 30CZ,FZ Auxiliary relay (check) X1 Contactor (fan O/D) TB1~3 Terminal block S
M(4)RT120A ARRANGEMENT Symbol Caution, 1. To protect each Fan motor and Compressor from abnormal current, Over current relays <51C>, <51F> are installed. Therefore, do not change factory set value of Over current relays. Note: 1. The dotted lines show field wiring. 2. The figure in the parentheses shows field supply parts. 3. Color of earth is yellow and green twisting. 4. If the power supply is 380AV, change the “C03” connector with silver color tape to red color tape. 5.
MRT150A MRT200A (MECHANICAL CONTROL) MRT150/200A Symbol Name MC1,2 MF1 Compressor motor Fan motor (indoor) MF2,3 52C1,2 Fan motor (outdoor) Contactor (compressor) 52F1 Contactor (fan I/D) 52F2 TB1,2 Contactor (fan O/D) Terminal block F1, F2 Fuse (3.
MRT150AR MRT200AR Symbol MC1,2 (STANDARD : MECHANICAL CONTROL) Fig. 1 Control box layout Name Symbol Name Compressor motor TCZ Timer MF1 Fan motor (indoor) Switch (Operation mode) MF2,3 Fan motor (outdoor) Switch (on) 52C1,2 Contactor (compressor) <23WA> Thermostat (room temp.) 52F Contactor (fan I/D) 49F1,2 Internal thermostat (fan O/D) TB1~3 Terminal block 49C1,2 Internal thermostat (compressor) F1, F2 Fuse (3.
MRT250A MRT300A (STANDARD: IC CONTROL) Symbol Name MC1,2 Compressor motor MF1 Fan motor (indoor) MF2,3 Fan motor (outdoor) 52C1,2 Contactor (compressor) 52F1 Contactor (fan I/D) 51C1,C2 Overload Protector (compressor) TB1,2,3 Terminal block F1 Fuse (3.
M(4)RT250AR M(4)RT300AR (STANDARD: IC CONTROL) Symbol Name MC1,2 Compressor motor MF1 Fan motor (indoor) MF2,3 Fan motor (outdoor) 52C1,2 Contactor (compressor) 52F1 Contactor (fan I/D) 52F2,3 Contactor (fan O/D) 51C1,C2 Overload Protector (compressor) TB1,2,3 Terminal block F1 Fuse (3.
M(4)RT080A M(4)RT100A (STANDARD: IC CONTROL) Symbol Name MC Compressor motor MF1 Fan motor (indoor) MF2 Fan motor (outdoor) 52C Contactor (compressor) 52F1 Contactor (fan I/D) 51C Over current realy (comp) TB1,2 Terminal block F1 Fuse (3.
M(4)RT150A M(4)RT200A (STANDARD: IC CONTROL) Symbol MC1, 2 Name Compressor motor MF1 Fan motor (indoor) MF2,3 Fan motor (outdoor) 52C1,2 Contactor (compressor) 52F Contactor (fan I/D) TB1,2,3 Terminal block F1 Fuse (3.
M4RT080AR M4RT100AR (STANDARD: IC CONTROL) M4RT80/100AR…60A Note : 1. The dotted lines show field wiring. 2. The figure in the parenthesis show field supply parts. 3. Color of earth wire is yellow and green twisting. 4. Specification subject to change without notice. Caution, 1. To protect each Fan motors and Compressors from abnormal current, overcurrent relays <51F1>, <52C> are installed. Therefore, do not change factory set value of these overcurrent relays.
MRT080AR MRT100AR (OPTIONAL: IC CONTROL) MRT80/100AR…60A Note : 1. The dotted lines show field wiring. 2. The figure in the parenthesis show field supply parts. 3. Color of earth wire is yellow and green twisting. 4. Specification subject to change without notice. Caution, 1. To protect each Fan motors and Compressors from abnormal current, overcurrent relays <51F1>, <52C> are installed. Therefore, do not change factory set value of these overcurrent relays.
Installation All series of air conditioners are designed for outdoor installations and are to be placed on a slab or rooftop, however if the air conditioner is to be installed in a plant room application, please contact your equipment supplier prior to installation. Access for both service and installation must be provided to the compressors, control wiring and fans as shown below. 1. Space Required Around Units. (1) Care must be taken to prevent recirculation air.
MRT250/300 A/AR 2. Installation Of The Unit. (1) The figure shows the use of the roof curb available for mounting these units. (2) The curb should be sealed and fixed to the roof by weather stripping. A suggested means of sealing the unit and roof curb is shown below. 3. Duct Construction. (1) Series MRT side flow units are equipped with horizontal supply and return air openings.
4. Lifting Method. When the unit is to be lifted and moved, attach ropes to the suspension plates (4 p.c.s) provided on the top of the unit. When the unit is lifted, it is center of gravity tends to shift the unit one side and so balance, such as that in the figure below, should be attained. The angles at which the ropes suspend the unit should be at least 60° at the compressor end and at least 45 ° at the condenser end. Care should be taken to avoid contact with the main unit while carrying.
Special Precautions For R407C Special Precautions When Dealing With Refrigerant R407c Unit 1) What is new refrigerant R407C? R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus conformed to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.
c) Ensure that the compressor is not expose to open air for more than the recommended time specified by its manufacturer (typically less than 10 minutes). Removed the seal-plugs only when the compressor is about to be brazed. d) The system should be thoroughly vacuumed to 1.0 Pa (-700mmHg) or lower. This vacuuming level is more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
8. CONTROLLER 8.1 GLOBAL REMOTE CONTROLLER (PAC-204RC): MODEL: MRT080/100/150/200A/AR CONFIRMATION OF PARTS The following parts are contained in the carton box together with this manual. Please check to make sure that everything is included. Q’TY c Remote controller (upper case, lower case) ................................................................ 1 d Pan-head screw with cross hole M4............................................................................ 2 e Wooden screw 4.
SETTING DIP SWITCH Set the DIP switches on the basis of the below table. Factory pre setting DIP switch 1 ON OFF MRT setting MRT-AR setting FUNCTION Mode select DIP switch 2 ON OFF (Not change) (Not change) (Not change) (Not change) (Not change) Cooling only Fan speed Hi / Lo (*1) Do not change DIP switch 2 Auto change over function (*2) Available Not Available Auto start at power failure (*3) Note.
b) SELECTING OPERATION WHEN SELECTING OPERATION c Press the [MODE] button Consecutive press of the [MODE] button switches the operation over to "FAN" , "COOL" or “HEAT”. For the contents of operation, check the display. FOR FAN Press the [MODE] button and bring up the "FAN" display. • The fan operation functions to circulate the air in the room. • The temperature of the room cannot be set by fan operation. CAUTION: Never expose your body directly to cool air for a long time.
d) TIME SETTING d CLOCK KEY c Press the key one time will activate set clock mode. Press the key again will disable set clock mode. ~ f Under set clock mode, the real time clock and present day setting can be changed by pressing Day key, Hour key or Minute key. 7-DAYS TIMER KEY c There are two keys for timer. One is ON Timer, another is d Off Timer. Press the key one time will activate set timer mode. Press the key again will disable set timer mode.
8.2 SLM WIRED CONTROLLER (MODEL : M4RT080/100A/AR; MODEL: MRT080/100 A/AR OPTIONAL) 1. “ON/OFF” switch • Press to start the air conditioner unit. • Press again to stop the unit. 5. Timer. •Press the set button to select the switch timer of the air conditioner unit (the setting range is between 1 to 10 hours). 2. Temperature setting • Set the desired room temperature. • Press button to increase or decreaseo the set temperature. Setting range are between 16 C to 30oC (60oF to 80oF). 6.
8.
7-days timer Press the ON TIMER key to activate auto-ON timer mode. Under this mode, press the respective MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to automatically start running. Press the ON TIMER key again to save the setting. Press the OFF TIMER key to activate auto-OFF timer mode. Under this mode, press the respective MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to automatically stop running.
iii) iv) Connect one end in each of the 4 wires to the terminal block behind the top case as shown below. The wire that goes into the "GND" terminal at the top case must be connected at the other end to the “GND" terminal at the main board. The same goes for the "+5V", "B" and "A" connection. Fasten back the top and bottom case into place. Hook the two upper claws into their respective slots and snap the lower part shut.
9. ELECTRIC WIRING Construct the earth connection. All electrical work must be carried out by a suitable qualified electrical trades-person and in accordance with local supply authority requirements and associated regulators. The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse. Fix power source wiring to control box by using buffer bushing for sensible force (PG connection or the like).
Control module of unit (MRT250/300AR, M4RT250/300AR) (STANDARD) Control module of unit (MRT250/300A, M4RT250/300A (STANDARD) Method for connecting electric wire Please do the wiring after consulting the electric power company of jurisdiction beforehand in the instruction. (I) The entire wiring diagram of unit. MRT060~300A/AR a. b. c. d. e. Power supply Main switch/fuse (field supply) Power supply wiring for unit Unit Remote controller Connection wiring for unit / remote f. controller (no polarity) g.
Control module of unit (MRT080/100AR) (Optional: IC control) Control module of unit (M4RT080/100AR) (Standard: IC control) 86
Control module of unit (MRT150/200AR) (Optional: IC control) Control module of unit (M4RT150/200AR) (Standard : IC control) 87
MRT080/100AR MRT150/200AR MRT080/100AR MRT150/200AR (III) Wiring example and selection of earth leakage breaker 380~415V, 50Hz, 3∅ Model MRT060A/AR MRT080A/AR MRT100A/AR MRT120A/AR MRT150A/AR MRT200A/AR MRT250A/AR MRT300A/AR Power cable Breaker capacity Over current protection switch Earth cable Fuse (class B) 8 mm2 40A 40A 8 mm2 over 14 mm 2 14 mm 2 14 mm 2 22 mm 2 22 mm 2 38 mm 2 60 mm 2 50A 50A 50A 100A 100A 125A 175A 50A 50A 50A 100A 100A 125A 175A Earth leakage breaker (wi
10. THE PUTTING CONDITION OF THE BELT 1. Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below. 2. Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1 and table 2 below at the proper flexion. (A=0.016xC mm) 3. Adjust the suitable tension after the belt sit properly across the pulley (after working for 24-28 hours). When the new belt is used, adjust the suitable tension about the 1.
Servicing And Maintenance FOR SUPERIOR PERFORMANCE AND LASTING DURABILITY, PLEASE DO NOT FORGET TO CONDUCT PROPER AND REGULAR MAINTENANCE. Warning 1.Do not wash the unit with water. If washed with water, electrical shock may be caused. 2.Ahead of the maintenance. For safety, turn the power source off before service work. 1.
1.5 When The Air Conditioner Is Not To Be Used For Long Time. If the air conditioner is not to be used for a long time due to a seasonal change, etc., Please do the following work. 1. The power supply switch is turned off. If the power supply is kept on, several watts or several tends of watts will be wasted. Also, the accumulation of dust, etc., can result in fire. 2. Filter, eliminator and drain pan are cleaned. Pay attention to throw dust in the drain. 3.
2.5 Disposing Of The Unit. When you need to dispose of the unit, consult your dealer. If pipes are removed incorrectly, refrigerant (fluorocarbon gas) may blow out and come into contact with your skin, causing injury. Releasing refrigerant into the atmosphere also damages the environments. 2.6 Maintenance And Inspection. (1) If the air conditioner is used throughout several seasons, inside can get dirty and eventually reduce the performance.
Part List Model : MRT060A NO DESCRIPTION NO 1 ASSY. INS. BASE PAN 24 SUPPORT, PARTITION 2 STRUCTURE BASE RIGHT 25 PARTITION, TUBING 3 STRUCTURE BAE LEFT 26 ASSY. COMPRESSOR 4 ASSY. INS. PARTITION 27 HEATER, CRANKCASE 5 ASSY. PILLAR INDOOR 2 28 ASSY. TUBING 6 ASSY. PILLAR 1 29 ASSY. PILLAR OUTDOOR LEFT 7 SUPPORT, COIL BASE 30 ASSY. PILLAR OUTDOOR RIGHT 8 FRAME, OUTDOOR 1 31 ASSY. REAR TOP PANEL 9 FRAME, OUTDOOR 2 32 ORIFICE, BELL MOUTH 10 ASSY.
Model : MRT080/100 A/AR NO DESCRIPTION NO NO DESCRIPTION 1 ASSY. BASE INDOOR 32 ASSY. COVER BLOWER DESCRIPTION 63 PULLEY, B1 x 4.5 x 24mm NBK 2 ASSY. BASE OUTDOOR 33 ASSY. PILLAR INDOOR 1 64 PULLEY, BLOWER B1 x 6 x 20mm 3 ASSY. BASE OUTDOOR 34 ASSY. PILLAR INDOOR 2 65 BELT, V B30 BANDO 4 STRUCTURE BASE RIGHT 35 ASSY. FRONT PANEL 66 BELT, V B31 BANDO 5 STRUCTURE BASE LEFT 36 ASSY. BEAM FRONT 67 SUPPORT, PARTITION 6 ASSY. PARTITION 37 ASSY. COIL INDOOR (PRG8) 68 ASSY.
Model : MRT120A NO 1 DESCRIPTION NO DESCRIPTION NO DESCRIPTION ASSY. BASE INDDOOR 31 ASSY. BLOWER HOUSING A 61 ASSY. INTAKE DUCT 2 ASSY. BASE OUTDOOR 32 ASSY. BLOWER HOUSING B 62 ASSY. DISCHARGE DUCT 3 STRUCTURE BASE RIGHT 33 FAN SIROCCO, D286 x L274 PLASTIC 63 PANEL, SERVICE 1 4 STRUCTURE BASE LEFT 34 FAN SIROCCO, D286 x L184 64 PANEL, SERVICE 2 5 ASSY. PARTITION 35 SHAFT, FAN 65 HANDLE 6 ASSY. SUPPLY AIR 36 SHEET, RUBBER 38 x 165mm 66 BRACKET, FITTING 7 ASSY.
Model: MRT150/200A/AR NO DESCRIPTION NO 1 ASSY. BASE OAN OD 36 ASSY.FRAME MOTOR DESCRIPTION 71 NO DESCRIPTION ASSY. COIL OUTDOOR L RT200A 2 ASSY. BASE FRAME REAR 37 ASSY. MOTOR BASE 72 ASSY. COIL OUTDOOR R RT200A 3 ASSY. BASE PAN ID (INS) 38 WASHER, MOTOR BASE 73 ASSY. COIL OUTDOOR L RT150AR 4 ASSY. SEPARATOR (INS) 39 MOTOR, 2.2kW 50Hz R P714568X01 HITACHI 74 ASSY. COIL OUTDOOR R RT150AR 5 ASSY. SEPARATOR (INS) 40 MOTOR3.7kW 50Hz R P714569X01 HITACHI 75 ASSY.
Model: MRT250/300A/AR NO DESCRIPTION NO NO DESCRIPTION 1 ASSY. BASE FRAME REAR 31 ASSY. FILTER RAIL CENTER DESCRIPTION 61 ASSY. TUBING RT250AR 2 ASSY. BASE FRAME FRONT 32 RAIL FILTER 2 62 ASSY. TUBING RT300AR 3 PLATE, BASE 33 ASSY. FILTER COVER (INS) 63 PANEL, SEPARATOR 3 4 FIXTURE 34 ASSY. PANEL FRONT TOP L (INS) 64 ASSY. SEPARATOR 2 5 ASSY. RIGHT BASE PANEL (INS) 35 ASSY. PANEL FRONT TOP R (INS) 65 ASSY. REAR TOP PANEL 6 ASSY.
REGISTERED ISO 9002 ©2004 McQuay International +1 (800) 432-1342 www.mcquay.