Specifications
74
General Data - Heat pump (R407C)
Btu/h 345000 374000
W 101110 109610
Btu/h 349000 431000
W 102290 126310
W 43170 48200
W 41670 46800
A 74.2 82.9
A 72.0 81.1
V/Ph/Hz
W/W 2.34 2.27
W/W 2.45 2.70
AIR DISCHARGE
OPERATION
AIR FLOW l/s / cfm 5191 / 11000 5899 / 12500
EXTERNAL STATIC PRESSURE Pa/in.wg.
mm/in
l/s / cfm
dBA
mm/in
mm/in
mm/in
mm/in
mm/in
mm/in
kg/lb 1510 / 3329 1600 / 3527
kg/lb 13.5/ 29.7 & 16 / 35.32 x 16 / 2 x 35.3
9439 / 20000
70
EER
COP
M4RT360AR M4RT420AR
380 ~ 415 / 3 / 50
294 / 1.18
DUCTED
SEQUENTIAL CONTROLLER
R407C / TXV
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
DEPTH
MODEL
CONTROL
EVAPORATOR*
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
2252 / 89.0
CONDENSER*
PACKING DIMENSION
HEIGHT
WIDTH
DEPTH
HEIGHT
WIDTH
REFRIGERANT CHARGE
AIR FLOW
UNIT WEIGHT
3250 / 128.0
2300 / 90.5
CONDENSATE DRAIN SIZE
UNIT DIMENSION
SOUND PRESSURE LEVEL
25.4 / 1
1974 / 78.0
3180 / 125.0
2150 / 84.5
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
5) * DESIGNATION BASED ON COOLING CYCLE.
6) EFFECTIVE POWER INPUT IS USED IN THE RATED EER/COP CALCULATION, ACCORDING TO ISO STANDARD: ISO 13253