Specifications
110
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Indoor WB
˚C
Indoor DB
˚C
Outdoor DB, ˚C
35
TC
(kW)
SHC
(kW)
25
......
55.29 46.30
PI
(kW)
37 40
TC
(kW)
SHC
(kW)
PI
(kW)
20.41 49.85 42.33 22.07x y z
Total capacity, TC
Interpolation Method:
40º C – 35º C
=
49.85kW – 55.29kW
49.85kW – xkW
40º C – 37ºC
x = 53.11kW
Sensible capacity, SHC
Interpolation Method:
40º C – 35º C
=
42.33kW – 46.30kW
40º C – 37º C
y
= 44.71kW
42.33kW – ykW
Power Input, PI
Interpolation Method:
40º C – 35º C
=
22.07kW – 20.41kW
40º C – 37º C
z = 21.07kW
22.07kW – zkW
17
TC
(kW)
SHC
(kW)
PI
(kW)