Specifications
109
Indoor WB
˚C
Indoor DB
˚C
Outdoor DB,˚C
40
TC (kW)
....
....
........................
48.47
17 25
x
6
y
6
19
16
52.61
45.38
36.24
z
6
21.93
22.35
Total capacity, TC
Sensible capacity, SHC
Interpolation Method:
19ºC – 16ºC
=
52.61kW – 48.47kW
52.61kW – x
6
kW
19ºC – 17ºC
x
6
= 49.85kW
(b) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 40°C DB
SHC (kW) PI (kW)
Interpolation Method:
19ºC – 16ºC
=
36.24kW – 45.38kW
36.24kW – y
6
kW
19ºC – 17ºC
y
6
= 42.33kW
Power Input, PI
Interpolation Method:
19ºC – 16ºC
=
22.35kW – 21.93kW
22.35kW – z
6
kW
19ºC – 17ºC
z
6
= 22.07kW