Specifications

106
Details:
1
st
Step:
Indoor WB
˚C
Indoor DB
˚C
Outdoor DB, ˚C
35
TC (kW)
16
25
.......................
x
1
y
1
24 53.36
54.44
47.36
54.22
20.24
20.33
27
Total capacity, TC
Interpolation Method:
27º C – 24º C
=
54.44kW
– 53.36kW
27º C – 25º C
x
1
= 53.72kW
Sensible capacity, SHC
Interpolation Method:
27º C – 24º C
27º C – 25º C
=
54.22kW
– 47.36kW
y
1
= 49.65kW
To obtain the Total capacity and Sensible capacity and Power input for
(a) Indoor Condition: 25˚C DB, 16˚C WB
Outdoor Condition: 35°C DB
54.44kW – x
1
kW
54.22kW – y
1
kW
Power Input, PI
Interpolation Method:
27º C – 24º C
27º C – 25º C
=
20.33kW
– 20.24kW
z
1
= 20.27kW
20.33kW – z
1
kW
SHC (kW)
z
1
PI (kW)