Specifications

17
Installation
Caution
Sharp edges and coil surface are potential injury hazard. Avoid from contact with them.
(1) INSTALLATION OF INDOOR UNIT
Preliminary Site Survey
Electrical supply and installation shall conform to the local authority (eg. National Electrical Board).
Voltage supply fluctuation must not exceed ±10% of the rated voltage. Electricity supply lines must be
independent of welding transformers which can cause high supply fluctuation.
Ensure that the installation location is convenient for wiring and piping.
Standard Mounting
Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods
(wall mounting bracket for floor standing), and check for its alignment with the unit as shown in Figure A.
Also, check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal
directions, taking into account the gradient for drainage flow as recommended in Figure B.
Model
MCM 020D/DR MCM025D/DR MCM030D/DR MCM040D/DR MCM050D/DR
A
1214 1214 1214 1714 1714
B
666 666 666 666 666
C
273 273 273 273 273
D
130 130 130 130 130
F
1160 1160 1560 1560 1560
G
27 27 27 27 27
H
77 77 77 77 77
I
745 745 745 1235 1235
J
25 25 25 25 25
K
209 209 209 331 331
L
486 486 486 486 486
M
108 108 108 108 108
N
360 360 360 600 600
O
770 770 770 1270 1270
P
136 136 136 136 136
Q
373 373 373 373 373
R
222 222 222 310 310
Note : Dimensions in mm
Figure A
Figure B