Specifications

85
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 37°C DB
Outdoor DB ° C
Indoor DB Indoor WB 35 37 40
° C ° C TC SHC PI TC SC PI TC SC PI
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
25 17 20.46 16.91 8.38 xyz18.48 15.47 9.06
Total capacity, TC
Interpolation Method:
x = 19.66kW
Sensible capacity, SHC
Interpolation Method:
y = 16.33kW
Power Input, PI
Interpolation Method:
z = 8.65kW
37°C - 35°C
=
x - 20.46kW
40°C - 35°C 18.48kW - 20.46kW
37°C - 35°C
=
y - 16.91kW
40°C - 35°C 15.47kW - 16.91kW
37°C - 35°C
=
z - 8.38kW
40°C - 35°C 9.06kW - 8.38kW