Specifications
83
Outdoor DB ° C
Indoor DB Indoor WB 35
° C ° C TC (kW) SC (kW) PI (kW)
16 19.88 18.13 8.32
17 25 x
5
y
5
z
5
19 21.62 14.46 8.49
2
nd
Step:
To obtain the Total capacity and Sensible capacity and Power Input for
(a) Indoor Condition: 25°C DB, 17°C WB
Outdoor Condition: 35°C DB
Total capacity, TC
Interpolation Method:
⇒
⇒
x
5
= 16.91kW
Sensible capacity, SHC
Interpolation Method:
⇒
⇒ y
5
= 17.73kW
Power Input, PI
Interpolation Method:
⇒
⇒ z
5
= 8.38kW
17°C - 16°C
=
x
5
- 19.88kW
19°C - 16°C 21.62kW - 19.88kW
17°C - 16°C
=
y
5
- 18.13kW
19°C - 16°C 14.46kW - 18.13kW
17°C - 16°C
=
z
5
- 8.32kW
19°C - 16°C 8.49kW - 8.32kW