Specifications

82
(b) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 40°C DB
Outdoor DB ° C
Indoor WB Indoor DB 40
° C ° C TC (kW) SHC (kW) PI (kW)
24 17.77 15.84 8.99
16 25 x
2
y
2
z
2
27 18.27 18.05 9.04
Total capacity, TC
Interpolation Method:
x
2
= 17.94kW
Sensible capacity, SHC
Interpolation Method:
y
2
= 16.58kW
Power Input, PI
Interpolation Method:
z
2
= 9.01kW
* Repeat process (a) and (b) in 1st step for the condition below:
(c) Indoor Condition: 25°C DB, 19°C WB
Outdoor Condition: 35°C DB
x
3
= 21.62kW
y
3
= 14.46kW
z
3
= 8.49kW
(c) Indoor Condition: 25°C DB, 19°C WB
Outdoor Condition: 40°C DB
x
4
= 19.47kW
y
4
= 13.24kW
z
4
= 9.17kW
25°C - 24°C
=
x
2
- 17.77kW
27°C - 24°C 18.27kW - 17.77kW
25°C - 24°C
=
y
2
- 15.84kW
27°C - 24°C 18.05kW - 15.84kW
25°C - 24°C
=
z
2
- 8.99kW
27°C - 24°C 9.04kW - 8.99kW