81
Details:
1
st
Step:
To obtain the Total capacity and Sensible capacity and Power input for
(a) Indoor Condition: 25°C DB, 16°C WB
Outdoor Condition: 35°C DB
Total capacity, TC
Interpolation Method:
⇒
⇒
x
1
= 19.88kW
Sensible capacity, SHC
Interpolation Method:
⇒
⇒ y
1
= 18.13kW
Power Input, PI
Interpolation Method:
⇒
⇒ z
1
= 8.32kW
25°C - 24°C
=
x
1
- 19.75kW
27°C - 24°C 20.15kW - 19.75kW
25°C - 24°C
=
y
1
- 17.30kW
27°C - 24°C 19.80kW - 17.30kW
25°C - 24°C
=
z
1
- 8.31kW
27°C - 24°C 8.35kW - 8.31kW
Outdoor DB ° C
Indoor WB Indoor DB 35
° C ° C TC (kW) SHC (kW) PI (kW)
24 19.75 17.30 8.31
16 25 x
1
y
1
z
1
27 20.15 19.80 8.35