Specifications
Servicing and Maintenance
Warning: Disconnect from main supply before servicing
 the air conditioner.
The unit is designed to give long life operation with minimum maintenance required. However, it should be
regularly checked and the following items should be given due attention.
Components Maintenance Procedure  Recommended Schedule 
Air filter 
(Indoor Unit) 
1.  Remove the ionizer filter before cleaning the filter. 
2.  Remove the dust adhering on the filter by using a 
vacuum cleaner or wash using water less than 40°C 
with a neutral cleaning detergent. 
3.  Rinse and dry it before fitting back the ionizer filter and 
set it back to unit. 
4. Note : Never use petrol thinner, benzene or any 
other chemicals. 
At least once a month. 
Indoor unit  1. Clean away dirt or dust on grille or panel by wiping with 
soft cloth soaked in lukewarm (or cool) water or 
neutral detergent solution. 
2. Note : Never user petrol, thinner, benzene or other 
 volatile chemicals, which may cause plastic surface 
 to deform. 
At least once a month. 
Condense Drain 
Pan & Pipe 
1.  Check the cleanliness and clean it if necessary. 
2.  Check the condensate water flow. 
Every 3 months. 
Indoor Fan  Check if there is any abnormal noise.  If necessary. 
Indoor/ Outdoor 
Coil 
1.  Check and remove the dirt between the fins. 
2.  Check and remove any obstacles which hinder air 
 flow through the indoor or outdoor. 
Every month. 
Power Supply  1. Check the running current and voltage for indoor and 
outdoor unit. 
2. Check the electrical wiring and tighten the wire onto 
 the terminal block if necessary. 
Every 2 months. 
Every year. 
Compressor  No maintenance needed if refrigerant circuit remains 
sealed. However, check for refrigerant leak at joint and 
fitting. 
Every 6 months. 
Compressor 
Oil 
Oil is factory charged. Not necessary to add oil if circuit 
remains sealed. 
No maintenance required. 
Fan Motor 
Oil 
All motors are pre-lubricated and sealed at factory.  No maintenance required. 
Pre Start Up Maintenance
(After Extended Shutdown)
- Inspect thoroughly and clean indoor and outdoor units.
- Clean or replace air filters.
- Clean condensates drain line.
- Clean clogged indoor and outdoor coils.
- Check fan imbalance before operation.
- Tighten all wiring connections and panels.
- Check for refrigerant leakage.
! 
212