Installation manual
Installation and operation manual
7
EKCC7-W
Central control for hydroboxes
4P341705-1 – 2013.02
6.3. Alarm menu
Press the alarm button to access the following screen:
Alarm list
Shows a list of the current alarms.
7. Troubleshooting
MDB is shown in the ‘Unit info’ menu.
Make sure that the Modbus connection to the RTD-W with the
corresponding address is correct.
Make sure that the correct number of connected units is defined
in the installer settings.
U5 is shown in the ‘Unit info’ menu.
Make sure that the P1P2 connection to the RTD-W with the
corresponding address is correct. If so, interrupt the power to the
RTD-W and apply it again.
Some lines are not available in the menus.
Interrupt the power to the EKCC7 central control, make the
correct installer settings, and apply the power again.
Room mode cannot be set. The text "Not available. By external
contacts" appears.
Room mode can only be set by external contacts from the
thermostat. To set the mode on the central control, change the
installer settings.