Specifications

Page 25
Outdoor Unit
Model MDS220B MDS220BR MDS240B MDS240BR MDS260B MDS260BR MDS280B MDS280BR MDS300B MDS300BR
Cooling capacity kW 55.0 55.0 65.0 65.0 70.0 70.0 75.0 75.0 80.0 80.0
Heating capacity kW - 58.0 - 68.0 - 75.0 - 80.0 - 85.0
Power supply 380V/3N
/50Hz
Sound level
dB(A) 66 66 68 68 68 68 69 69 69 69
Dimension mm 1990x840x1840 2280x840x1840 2580x840x1840
Weight kg 560 590 570 600 645 675 710 740 710 740
Cooling rated power input
kW 16.7 16.7 19.8 19.8 21.3 21.3 22.8 22.8 26.2 26.2
Cooling rated current
A 32.7 32.7 38.5 38.5 40.0 40.0 42.5 42.5 46.5 46.5
Heating rated power input
kW - 16.2 - 18.5 - 20.9 - 22.0 - 23.6
Heating rated current
A- 31.0 - 33.8 - 37.2 - 41.0 - 43.1
Refrigerant R22
Gas pipe
Solder, flange connection
Liquid pipe
Flare and threaded connection
mm(in) 19.05(3/4) 19.05(3/4)
mm(in) 38.1(1 1/2) 41.3(1 5/8)
Liquid pipe outside diameter
Gas pipe outside diameter
Pipe
connect
type
Model
MDS080B MDS080BR MDS100B MDS100BR MDS120B MDS120BR MDS150B MDS150BR MDS180B MDS180BR MDS200B MDS200BR
Cooling capacity kW 24.5 24.5 28.0 28.0 32.5 32.5 40.0 40.0 47.5 47.5 50.0 50.0
Heating capacity kW - 26.0 - 30.0 - 34.0 - 43.0 - 50.0 - 53.0
Power supply 380V/3N
/50Hz
Sound level
dB(A) 62 62 64 64 66 66 67 67 66 66 66 66
Dimension mm 990x840x1840 1290x840x1840 1990x840x1840
Weight kg 275 290 285 300 290 305 355 370 520 550 560 590
Cooling rated power input
kW 7.5 7.5 8.5 8.5 9.8 9.8 12.9 12.9 14.1 14.1 15.2 15.2
Cooling rated current
A 14.6 14.6 16.8 16.8 18.8 18.8 23.1 23.1 28.2 28.2 31.1 31.1
Heating rated power input
kW - 7.2 - 8.3 - 9.0 - 11.1 - 13.2 - 14.7
Heating rated current
A- 13.6 - 15.7 - 16.7 - 22.6 - 27.1 - 29.4
Refrigerant R22
Gas pipe
Solder, flange connection
Liquid pipe
Flare and threaded connection
mm(in) 12.7(1/2) 15.88(5/8)
mm(in) 28.6(1 1/8) 34.9(1 3/8)
Pipe
connect
type
Liquid pipe outside diameter
Gas pipe outside diameter
Notes:
The above cooling capacity is based on 27/19
o
C (DB/WB) indoor air temperature, 35/24
o
C (DB/WB) outdoor
air temperature.
Heating capacity is based on 20/15
o
C (DB/WB) indoor air temperature, 7/6
o
C outdoor air temperature.
Sound values are obtained before delivery. They may differ in practice due to environmental sound or other
reasons.