Specifications
Page 18
Ceiling Concealed Indoor Units MCC Series
Features
Central air conditioning miniaturization, slim body, concealed type, spacing saving. ESP is optional, intelligent
control and low noise.
Specifications
Model
MCC MCC MCC MCC MCC MCC MCC MCC MCC MCC
008T 010T 015T 018T 020T 025T 030T 040T 050T 060T
Cooling capacity W 2000 2500 3650 4500 5600 6500 7800 10600 12400 14400
Heating capacity W 2200 2600 3700 4700 6100 7400 8900 11600 14500 17300
Rated power input W 47 47 81 82 82 123 158 276 276 280
Power supply 220V
/50Hz
High m
3
/h 450 450 580 800 800 960 1200 1900 1900 2100
Air flow
Medium m
3
/h 370 370 470 650 650 780 950 1520 1520 1750
Low m
3
/h 280 280 380 540 540 600 800 1300 1300 1460
ESP(Options) Pa 15(0/30/50)
30(15/50/70)
50(15/30/70)
Dimension mm 1030x469x220 1290x490x250 1640x490x250
1900x490x250
Weight kg 22 22 22 25 25 27 28 39 39 45
Sound(High/medium/Low) dB(A) 31/29/27 31/29/27 34/32/30 35/32/29 35/32/29 37/36/35 42/40/38 47/45/43 47/45/43 48/46/44
Piping
Liquid pipe outside diameter
mm(in) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8) 9.52 (3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8) 9.52(3/8)
size
Gas pipe outside diameter
mm(in) 9.52 (3/8) 9.52 (3/8) 12.7 (1/2) 15.88(5/8) 15.88(5/8) 15.88(5/8) 15.88(5/8) 19.05(3/4)19.05(3/4) 19.05(3/4)
Drain pipe inch R3/4
Notes:
Cooling capacity is based on 27/19
o
C (DB/WB) indoor air temperature, 35/24
o
C (DB/WB) outdoor air temperature.
Heating capacity is based on 20/15
o
C (DB/WB) indoor air temperature, 7/6
o
C outdoor air temperature.
The heat pump indoor units are the same as the cooling only indoor units.
The ESP values in bracket are optional, and optional ESP can be easily reached on field.
Sound values are obtained before delivery. They may differ in practice due to environmental sound or other
reasons.