Service manual
Service Manual SM-MDS_(i)      87 
Emergency Run 
Error Code: EF, 1F (For MC301), ER60 (For MDS-M PCB) 
Replace outdoor PCB and restart the system 
Check the refrigerant 
charge. Is it within 
specification? 
NO 
Replace sensor and restart the 
system 
YES 
NO 
YES 
Find the root cause for 
communication error and solve it. 
Restart the unit 
Restart the unit 
Recharge refrigerant 
accordingly and restart the 
system 
Is there any communication 
error captured by the system? 
Is the resistance for 
sensor TH12 normal? 
Refer Appendix 7.5 
6 
YES 
NO 