Service manual
86     Service Manual SM-MDS_(i) 
Superheat protecting value too small 
Error Code: L0, 40 (For MC301), ER61 (For MDS-M PCB) 
Is the coil sensor (ID), 
TH12 sensor (OD) and 
low pressure sensor 
correctly connected? 
Connect correctly and operate 
again 
YES 
Recharging with correct amount of refrigerant 
NO 
Measure suction 
pressure. Within spec? 
NO 
Is the sensors resistance 
characteristics normal? 
Refer Appendix 7.3 & 7.5 
NO 
Replace sensor 
YES 
YES 
YES
NO 
Replace indoor/outdoor fan motor 
NO 
Replace EXV 
Turn on the unit 
YES 
Replace PCB 
Indoor fan motor 
(Cooling) / Outdoor fan 
motor (Heating) working? 
Is the indoor/outdoor 
EXV working properly? 
6 