Service Manual SM-MDS_(i)      83 
Indoor and controller communication error 
Error Code: F6 (For MC301) 
Is the wired controller 
connection loose? 
Connect correctly and operate again 
NO 
YES 
Replace the wired 
controller. Turn on 
the unit. Is the error 
remains? 
NO 
Restart the system and verify again 
YES 
Replace PCB. 
Turn off the unit 
Is the version of controller 
compatible with the indoor 
PCB? 
Refer Appendix 7.2 
YES 
NO 
Change controller or upgrade the 
software for controller/indoor unit PCB. 
Restart the system to verify 
6 
Is the wire exceed 
10m length? 
Connect correctly and operate again 
YES 
NO 