Service manual
80     Service Manual SM-MDS_(i) 
System malfunction error 
Error Code: Decorative Error code #8, E0, 10 (For MC301), E8 (For MDOM PCB), ER55 (For MDS-M PCB) 
YES 
Is the coil sensor and 
pressure sensor correctly 
connected? 
NO 
Ensure no obstacle around the unit 
and conduct inspection on coil and 
filter 
Connect correctly and operate 
again 
Sufficient airflow? 
YES 
NO 
Is the coil sensor and 
pressure sensor resistance 
characteristics normal? 
Refer Appendix 7.3 & 7.5 
NO 
Replace sensor 
YES 
YES 
NO 
Replace outdoor fan motor 
NO 
Replace ball valve 
Is the pressure 
switch functioning? 
YES 
NO 
Replace Pressure switch 
Is the EXV working 
properly? 
NO 
Replace EXV 
YES 
YES 
Turn on the unit 
6 
Outdoor fan motor working? 
Is the outdoor ball 
valve open/close 
normally? 