Service manual
Service Manual SM-MDS_(i)      77 
Compressor overload 
Error Code: Decorative Error code #7, H0 to H3, 30 to 33 (For MC301), H2 to H3 (For MDOM PCB), ER48 to 
ER51 (For MDS-M PCB) 
Is the overload protector 
current setting correct? 
Refer wiring diagram. 
Reset and restart the system 
YES 
NO 
Replace overload protector 
and restart the system 
Turn off the unit 
Is the refrigerant 
charge within spec? 
NO 
Recharge refrigerant accordingly 
and restart the s
y
stem
YES 
6 
Is the compressor 
resistance normal? 
Replace compressor 
YES 
NO 