72     Service Manual SM-MDS_(i) 
ER63 
Slave outdoor unit 
communication failure 
•  Master and slave communication wire broken 
•  Master and slave communication wire loose 
•  Master and slave communication wire A B reversed 
•  Slave unit power not on 
•  Master and slave jump wire not correct, still on update status 
•  Last outdoor unit terminal resistance of communication wire not short-circuit 
•  Master and slave PCB program not compatible. 
•  Master and slave PCB abnormal 
79 
ER64 
TH1 temperature 
sensor failure 
•  Outdoor discharge temperature sensor TH1 broken or loose 
ER65 
TH2 temperature 
sensor failure 
•  Outdoor 1# condenser inlet coil temperature sensor TH2 broken or loose 
ER66 
TH3 temperature 
sensor failure 
•  Outdoor 1# condenser midlet coil temperature sensor TH3 broken or loose 
ER67 
TH4 temperature 
sensor failure 
•  Outdoor 2# condenser inlet coil temperature sensor TH4 broken or loose 
ER68 
TH5 temperature 
sensor failure 
•  Outdoor 2# condenser midlet coil temperature sensor TH5 broken or loose 
ER71 
TH8 temperature 
sensor failure 
•  Outdoor ambient temperature sensor TH8 broken or loose 
ER72 
TH9 temperature 
sensor failure 
•  Outdoor outlet coil temperature sensor TH9 broken or loose 
ER73 
TH10 temperature 
sensor failure 
•  Outdoor sub-cool outlet temperature sensor TH10 broken or loose 
ER74 
TH11 temperature 
sensor failure 
•  Outdoor sub-cool suction temperature sensor TH11 broken or loose 
ER75 
TH12 temperature 
sensor failure 
•  Outdoor suction temperature sensor TH12 broken or loose 
73 
ER76 
High pressure sensor 
failure 
•  High pressure sensor communication wire broken 
•  Outdoor PCB HS port broken 
ER77 
Low pressure sensor 
failure 
•  Low pressure sensor connecting wire broken 
•  Outdoor PCB LS port broken 
74 
EC78 
All indoor units 
communication failure 
•  Indoor and outdoor communication wire broken 
•  Indoor and outdoor communication wire loose 
•  Indoor and outdoor communication wire A and B reversed 
•  Communication wire too long, should less than 1000m 
•  Outdoor PCB not power on 
•  Indoor and outdoor jump wire not correct, still on update status 
•  Last indoor unit terminal resistance of communication wire not short-circuit 
•  Indoor and outdoor PCB program not compatible 
•  Indoor and outdoor PCB abnormal 