Service manual

Service Manual SM-MDS_(i) 61
6.2 Error Code for Decorative Type Indoor
Page
Cool/Heat Sleep/Fan Dry/Timer
BLINKING OFF OFF
Communication error
Error Code #1
Description
Possible causes
Indoor and outdoor communication wire broken
Indoor and outdoor communication wire loose
Indoor and outdoor communication wire A and B reversed
Communication wire too long, should less than 1000m
Outdoor PCB not power on
Indoor and outdoor jumper not correct, still on update status
Last indoor unit terminal resistance of communication wire not short-circuit
Indoor and outdoor PCB program not compatible
Indoor and outdoor PCB abnormal
76
Cool/Heat Sleep/Fan Time/Dry
OFF OFF BLINKING
Indoor sensor error
Error Code #2
Description
Possible causes
Indoor sensor broken or loose
73
Cool/Heat Sleep/Fan Time/Dry
OFF BLINKING OFF
Indoor pump error
Error Code #3
Description
Possible causes
Water level switch broken
Indoor pump broken
75
Cool/Heat Sleep/Fan Time/Dry
OFF BLINKING BLINKING
Outdoor sensor error
Error Code #4
Description
Possible causes
Outdoor sensor broken or loose
73
Cool/Heat Sleep/Fan Time/Dry
BLINKING BLINKING ON
Outdoor pressure sensor error
Error Code #5
Description
Possible causes
High/low pressure sensor broken or loose
Outdoor PCB HS/LS port broken
74
6