Service manual
Service Manual SM-MDS_(i)      9 
Fan Speed 
Control 
Outdoor fan speed control (cooling mode) 
Outdoor fan speed control (heating mode) 
Protection 
Devices 
MDS system has several sensor and pressure switch for protection purpose: 
•  Discharge pressure protection (switch) 
•  Suction pressure protection (sensor) 
•  Discharge temperature protection for Digital Scroll Compressor 
• Compressor overload protection 
•  Fan motor overload protection 
Others 
For Fix Scroll Compressor: 
•  Minimum 3 minutes of start-up delay protection is available. 
For Digital Scroll Compressor: 
•  When digital compressor overloaded or discharge pressure too high, system will stop 
the outdoor for 3 minutes. System error will declare when outdoor unit stops for 3 times 
within 1 hour. 
• TH1 ≤ 105ºC – outdoor unit operates normally. 
• TH1 ≥ 130ºC – outdoor unit forced to stop. 
• 105ºC ≤ TH1 ≤ 130ºC for 2 minutes, outdoor unit enter protection mode. 