Specifications
MODEL : MCM050D / MLC050C 
Indoor 
DB 
Indoor 
WB 
Capacit
y 
Outdoor DB, °C 
°C °C kW 19.4 25 30 35 40 46 50 52 54 
26.7 13.9  TC 12.749 12.256 11.815 11.374 10.717 10.114  9.762  9.601  9.451 
    SC  11.176 11.014 10.869 10.724 10.104  9.535  9.204  9.052  8.910 
  15  TC  14.011 13.300 12.665 12.030 11.335 10.697 10.325 10.155  9.996 
    SC  10.996 10.774 10.575 10.377 9.777 9.227 8.906 8.760 8.622 
  18  TC  17.454 16.149 14.984 13.819 13.020 12.288 11.861 11.665 11.482 
    SC  10.505 10.119 9.775 9.431 8.886 8.386 8.095 7.961 7.836 
  19.4  TC  19.060 17.478 16.066 14.654 13.807 13.031 12.578 12.370 12.176 
    SC  10.275 9.814 9.402 8.990 8.470 7.994 7.716 7.589 7.469 
  20  TC  19.748 18.098 16.624 15.151 14.275 13.472 13.004 12.789 12.589 
    SC  10.177 9.681 9.238 8.796 8.287 7.821 7.549 7.425 7.308 
  22  TC  22.043 20.163 18.485 16.806 15.834 14.944 14.424 14.187 13.964 
    SC  9.849 9.239 8.694 8.149 7.678 7.246 6.994 6.879 6.771 
  24  TC  24.338 22.228 20.345 18.461 17.394 16.416 15.845 15.584 15.339 
    SC  9.522 8.797 8.149 7.502 7.068 6.670 6.439 6.332 6.233 
MODEL : MCM061/ 062C / MLC061C 
Indoor 
DB 
Indoor 
WB Capacity 
Outdoor 
DB, °C           
°C °C kW 19.4 25 30 35 40 46 
26.7 13.9  TC 15.426 14.631 13.922 13.213 12.504 11.653 
    SC  15.426 14.631 13.922 13.213 12.504 11.653 
  15  TC  16.454 15.520 14.687 13.853 13.019 12.019 
    SC  14.771 14.033 13.374 12.714 12.055 11.264 
  18  TC  19.260 17.945 16.772 15.598 14.425 13.016 
    SC  12.987 12.401 11.878 11.354 10.830 10.202 
  19.4  TC  20.569 19.077 17.745 16.413 15.080 13.482 
    SC  12.155 11.639 11.179 10.719 10.259  9.707 
  20  TC  21.130 19.590 18.215 16.840 15.465 13.815 
    SC  11.798 11.290 10.837 10.383  9.930  9.386 
  22  TC  23.001 21.301 19.783 18.265 16.747 14.925 
    SC  10.609 10.126 9.695 9.264 8.833 8.316 
  24  TC  24.871 23.011 21.350 19.689 18.028 16.035 
    SC  9.419 8.962 8.553 8.145 7.736 7.246 
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB,   
please use the formula below :   
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000   
Where,  BPF = Bypass factor 
  EDB = Entering dry bulb temperature, ° C 
MCM020D 
MLC020B 
MCM025D 
MLC025B 
MCM030D 
MLC030B 
MCM030D 
MLC030C 
MCM040D 
MLC035C 
MCM040D 
MLC040C 
MCM050D 
MLC050C 
MCM061C 
MLC061C 
Bypass factor 0.50 0.44 0.30 0.42 0.64 0.51 0.44 0.55 