CMWSC -2006 Split Water Source Heat Pump And Cooling Only Unit Models: MWSC 010 B/BR MWSC 025 B/BR MWSC 015 B/BR MWSC 030 B/BR MWSC 020 B/BR MWSC 050 B/BR
Contents Features ......................................................................................................................................2 Specifications .............................................................................................................................4 Outlines And Dimensions ..........................................................................................................7 Electrical Connection And Parameter .................................................
Features Save Energy This decentralized, year-round heating and cooling system consists of a two-pipe closed loop water circuit, through which non-refrigerated water circulates continuously throughout the building. Locating the piping within the building negates the need of for piping insulation. These systems achieve energy conservation by pumping heat from warm to cold spaces whenever they coexist anywhere within the building.
Microcomputer remote control The microcomputer remote control has following functions • Five optional operation modes (heat/cool/dry/fan/auto). • Fan speed can be set at high, medium, low and automatic. • Sleep mode automatically increase set temperature since temperature is lower at night thus achieving healthy sleep. • Microcomputer controlled thermostat precisely controls room temperature resulting in energy saving and increases comfort. • Hot start and hot keep mode do not supply air for 30 sec.
Specifications Ceiling Concealed Heat Pump Models Indoor unit MCC010M MCC010MR MCC015M MCC015MR MCC020M MCC020MR MCC025M MCC025MR MCC030M MCC030MR MCC050M MCC050MR Outdoor unit MWSC010B MWSC010BR MWSC015B MWSC015BR MWSC020B MWSC020BR MWSC025B MWSC025BR MWSC030B MWSC030BR MWSC050B MWSC050BR Model W Rated heating capacity W Indoor Unit Rated cooling capacity Air flow m³/h Power source V/Ph/Hz 2700 --- 4200 3000 --- 550 5600 4300 --- 760 5600 --- 1150 8200 7800 --- 12300 10500 1400 --
Ceiling Exposed Heat Pump Models Indoor Unit MCM020D MCM020DR MCM030D MCM030DR MCM050D MCM050DR Outdoor Unit MWSC020B MWSC020BR MWSC030B MWSC030BR MWSC050B MWSC050BR Model Cooling Capacity(W) 5250 5250 8200 8200 12300 12300 Heating Capactiy(W) - 5600 - 10500 - 14500 Power Source 220V~/50Hz 380V/3N~/50Hz Cooling 1495 1495 2350 2350 3060 3060 Heating - 1480 - 2360 - 3500 Cooling 7.3 7.3 11.1 10.8 5.7 7.0 Heating - 6.8 - 10.8 - 7.
Ceiling Cassette Heat Pump Models Indoor Unit MCK 020A Cooling Capacity W Heating Capacity W MCK 020AR MCK 030A 5,600 — MCK 030AR MCK 050A 8,200 5,600 — MCK 050AR 12,300 10,500 — 14,500 Liquid Pipe Φmm(in) 6.35 (1/4") 9.52 (3/8") 9.52 (3/8") Gas Pipe Φmm(in) 15.88 (5/8") 15.88 (5/8") 19.
Outlines and Dimensions Indoor unit model: MCC 010M /MCC 010MR 224 180 612 484 524 566 4-10x20 730 22 40 800 162 830 224 unit: mm Indoor unit model: MCC 015M / MCC 015MR 224 180 712 484 524 566 4-10x20 830 22 40 900 162 930 224 unit: mm Page 7
Indoor unit model: MCC 020M / MCC 020MR MCC 025M / MCC 025MR 965 258 262 270 R3/4 187 560 6-10x16 948 978 1290 208 118 250 560 280 13 unit: mm Indoor unit model: MCC 030M /MCC 030MR 1315 258 262 270 R3/4 187 1298 1337 1640 208 118 560 250 560 6-10x16 280 13 unit: mm Page 8
Page 9
Outdoor unit model: MWSC 015B/MWSC 015BR Piping size(mm) Liquid Gas Model φ6.35 φ12.7 411 381 329 MWSC025B/BR 637 698 4- 17 Water pipe outlet Rc1/2 Water pipe inlet Rc1/2 Liquid pipe 145 93 75 91 437 Gas pipe 170 83 736 unit: mm Outdoor unit model: MWSC 020B/MWSC 020BR Model φ9.52 φ15.
Outdoor unit model: MWSC 025B/MWSC 025BR Piping size(mm) Liquid Gas Model φ9.52 φ15.88 411 381 329 MWSC025B/BR 637 698 4- 17 Water pipe outlet Rc1/2 Water pipe inlet Rc1/2 84 64 92 437 Gas pipe 250 Liquid pipe 736 75 126 unit: mm Outdoor unit model: MWSC 030B/MWSC 030BR Piping size(mm) Liquid Gas Model 421 391 339 MWSC030B/BR 696 759 φ9.52 φ15.
Outdoor unit model:MWSC 050B/MWSC 050BR Piping size(mm) Liquid Gas Model 498 468 408 MWSC050B/BR 723 783 φ9.52 φ19.
Model : MCM 020 / 030 / 050 D MCM 020 / 030 / 050 DR B B A A C C G G F F E E I I J J D D L L PULL PULL PULL PULL PULL K K PULL M M PULL PULL H H MODEL MCM 020D/DR MCM 030D/DR MCM 050D/DR A 1174 1174 1674 B 75 75 75 C 1082 1082 1582 D 68 68 68 E 58 93 93 F 156 156 156 G 1214 1214 1714 H 57 57 57 I 670 670 670 J 216 216 216 K 319 319 319 L 879 879 1379 M 517 517 517 Page 13
MCK 020 / 030 / 050 A MCK 020 / 030 / 050 AR E H G J L I F C A B D K Model : M Note : Dimension in mm Model A B C D E F G H I J K L M MCK020A/AR 820 875 548 820 363 335 28 930 930 642 622 555 555 MCK030A/AR 820 875 548 820 363 335 28 930 930 642 622 555 555 MCK050A/AR 820 875 548 820 363 335 28 930 930 642 622 555 555 Page 14
Electrical Connection and Parameter 1) Electrical connection Model: MCC 010M / MWSC 010B MCC 015M / MWSC 015B Indoor terminal block The temperature sensor wire connecting outdoor unit with indoor unit Outdoor terminal block N COMP L The malfunction wire connecting outdoor unit with indoor unit F E1 E3 WV COMP N Connecting cable 220-240V Power supply cable There must be a double pole switch with minimum 3mm contact gap in the installation circuit.
Model: MCC 030M / MWSC 030B Indoor terminal block Outdoor terminal block The temperature sensor wire connecting outdoor unit with indoor unit L COMP L WV COMP N L N N Connecting cable E3 The malfunction wire connecting outdoor unit with indoor unit E2 F E1 220-240V Power supply cable 220-240V/1Ph /50Hz There must be a double pole switch with minimum 3mm contact gap in the installation circuit.
Model: MCC 050M / MWSC 050B 1) Electrical connection The temperature sensor wire connecting outdoor unit with indoor unit F E2 E1 The malfunction wire connecting outdoor unit with indoor unit Outdoor terminal block A Indoor terminal block LIVE E3 220-240V N COMP WV WV COMP N L L N Connecting cable T Power supply cable S 380-415V/3Ph-50Hz R There must be a three pole switch with minimum 3mm contact gap in the installation circuit.
1) Electrical connection Model: MCC 010MR / MWSC 010BR MCC 015MR / MWSC 015BR Indoor terminal block The temperature sensor wire connecting outdoor unit with indoor unit Outdoor terminal block L The malfunction wire connecting outdoor unit with indoor unit E3 WV 4WV COMP 4WV COMP N N Connecting cable E1 220-240V F Power supply cable There must be a double pole switch with minimum 3mm contact gap in the installation circuit.
Model: MCC 030MR / MWSC 030BR Outdoor terminal block Indoor terminal block The temperature sensor wire connecting outdoor unit with indoor unit 4WV COMP L WV 4WV COMP N L N N Connecting cable E3 L The malfunction wire connecting outdoor unit with indoor unit 220-240V E1 E2 F Power supply cable N E N L 220-240V/1Ph/50Hz L There must be a double pole switch with minimum 3mm contact gap in the installation circuit.
Model: MCC 050MR / MWSC 050BR 1) Electrical connection Indoor terminal block Outdoor terminal block F E2 E1 The malfunction wire connecting outdoor unit with indoor unit A The temperature sensor wire connecting outdoor unit with indoor unit L LIVE E3 220-240V N 4WV COMP WV N WV 4WV COMP L N Connecting cable T Power supply cable R S 380-415V/3Ph/50Hz There must be a three pole switch with minimum 3mm contact gap in the installation circuit.
Model : MCK 020A/ MWSC 020B MCK 030A/ MWSC 030B MCM 020D/ MWSC 020B MCM 030D / MWSC 030B 1) Electrical connection Indoor unit Outdoor unit Terminal block Terminal block Connecting cable N N COMP COMP A A W F F N L E N L Power supply wire 220-240/1Ph/50Hz There must be a double pole switch with minimum 3 mm contact gap in the fixed installation circuit.
Model : MCK 050A / MWSC 050B MCM 050D / MWSC 050B 1) Electrical connection Indoor unit Outdoor unit Terminal block Terminal block Connecting cable N N L L COMP COMP A A F F N Power supply wire 380-415V/3Ph/50Hz N T S R E T S R There must be a three pole switch with minimum 3 mm contact gap in the fixed installation circuit.
Model : MCK 020AR / MWSC 020BR MCM 020DR / MWSC 020BR MCK 030AR / MWSC 030BR MCM 030DR / MWSC 030BR 1) Electrical connection Indoor unit Outdoor unit Terminal block Terminal block Connecting cable N N COMP COMP 4WV 4WV A A W F F N L E N L There must be a double pole switch with minimum 3 mm contact gap in the fixed installation circuit.
Model : MCK 050AR / MWSC 050BR MCM 050DR / MWSC 050BR Indoor unit Outdoor unit Terminal block Terminal block Connecting cable N N L L COMP COMP 4WV 4WV A A F F N Power supply wire 380-415V/3Ph/50Hz There must be a three pole switch with minimum 3 mm contact gap in the fixed installation circuit.
Installation Of Indoor Unit Installation of MCC unit 1) Preliminary site survey Electrical supply and installation is to conform to local authorityʼs codes and regulations (e.g. National Electricity Board), Voltage supply fluctuation must not exceed ± 10% voltage. Voltage supply lines must be independent of welding transformers which can cause high voltage fluctuation. Ensure that the location is convenient for wiring and piping.
Item Description of Figure 2 1 Indoor unit 2 Flexible connector or plenum box 3 Air-supplying adaptor 4 Round duct 5 Air-distribution adaptor 6 Air-distribution box Model Recommended No.
4) Others ó Each supply and return air must be fixed with supporting frame onto the ceiling of concrete prefabricate. The duct joint section should be sealed with glue. ó Returning air-box is suggested to be more than 150mm away from the side wall starting from outer edge of box. ó The obliqueness of level of drainage pipe should be taken into account about 1% degree. ó Drainage pipe should be wrapped with insulation fiber.
Installation of MCK unit Preliminary site survey ó Electrical supply and installation is to conform to local authorityʼs (e.g. National Electrical Board) codes and regulations. ó Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of welding transformers, which can cause high supply fluctuation. ó Ensure that the location is convenient for wiring, piping and drainage.
Unit Installation ó Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the handing rod. ó The installation template is extended according to temperature and humidity. Check on dimensions in used. ó The dimensions of the installation template are as same as those in the ceiling opening dimensions. ó When ceiling lamination work is not completed, be sure to fit the installation template to the indoor unit.
Drain Piping Work ó ó ó ó ó Drainpipe must be in downward gradient for smooth drainage. Avoid the drainpipe in up and down slope to prevent reversed water flow. During the drain piping connection, be careful not to exert extra force on the drain connector at indoor unit. The outside diameter of the drain connection at the flexible drain hose is 20mm. Be sure to execute heat insulation (polyethylene foam with thickness more than 8.0mm) on the drain piping to avoid the condensed water dripping inside the room.
Note : Install the front frame panel firmly to prevent cool air leakage which will cause condensation and water dripping Indoor Unit Cool Air Cool Air Air leak Air leak Ceiling Board Ceiling Board Panel Good Installation Bad Installation Air intake grille installation ó ó ó ó ó Before installed the air intake grille, be sure to fix the ionizer filter to the air filter. Fix the ionizer filter to the air filter with the black side on top and white side at bottom. Carefully clip on the ionizer filter frame.
Installation of MCM unit Preliminary site survey ó Electrical supply and installation shall conform to the local authority (e.g. National Electrical Board). ó Voltage supply fluctuation must not exceed ± 10% of the rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fluctuation. ó Ensure that the installation location is convenient for wiring and piping.
Please ensure that following steps are taken: ó Check the gradient for drainage flow as recommended in Figure B. ó Provide clearance for easy servicing and optimal air flow as shown in Figure C. 10mm HIGHER 10mm FIGURE B PULL PULL PULL PULL ó The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air. FIGURE C Min 500mm Min 10mm Min 300mm Max 250mm UTENSILS, FURNITURES OR BUILT-IN ARCHITECTUAL FEATURES MUST NOT PROTURDE MORE THAN 250.
SEMI-ENCLOSE SCISSOR ó In case the unit is to be half-recessed into a false ceiling, please check that the unit is wellaligned. ó Provide the installation space as shown in figure D. FIGURE D 300 .0 62 1.0 10 .0 300 .0 10 .0 10. 0mm 10 mm TOP PANEL OF UNIT 166mm CEILING BOARD 10mm STEP 1: Remove the air intake grille, side panel, side close-up and hanger bracket from the unit. See Figure E.
STEP 2: Position the hanger rods as shown in Figure B, and install the hanger bracket. See Figure F. FIGURE F STEP 3: Hang up the unit and tighten the bolt. After completing the piping and draining pipe, install back the grille and panel. See Figure G. FIGURE G INSTALLATION-FLOOR STANDING TYPE STEP 1: Remove the air intake grille, side close-up and side panel from the unit. See Figure E. STEP 2: There are two types of piping and draining pipe connection, as shown in Figure H.
Installation Of Outdoor Unit The location of the outdoor unit is very flexible, it can be installed in ceiling, stairs, toilet and out wall or other places. In order to operate the unit reliable, precaution steps: 1) Leave enough space for service person to perform maintenance of repair and provide sufficient room to make water, electrical connections. 2) The place can withstand the weight of the outdoor unit and isolate the noise and vibration.
Refrigerant Piping Work Refrigerant piping is important in particular. Refrigeration cycle of the split air conditioner is realized by the perfect piping work. Piping length and elevation If the piping is too long, both the capacity and reliability of unit will drop. As the number of bends increase, resistance to flow of refrigerant system increases, thus lowering cooling capacity and as a result the compressor may become defective. Always choose the shortest path and follow the recommendation as tabulated.
Piping Connection 1) Do not use contaminated or damaged copper tubing. If any piping, evaporator or condenser had been exposed or had been opened for 15 seconds or more, then vacuum and purge with field supplied refrigerant. Generally, do not remove plastic, rubber plugs and brass nuts from the valves, fittings tubing and coils until it is ready to connect suction or liquid line into valves or fittings.
5) If systemʼs refrigerant is leaked, recharge refrigerant referring to following diagram.
Piping Works & Flaring Technique ó Do not use contaminated or damaged copper tubing. If any pipings, evaporator or condenser had been exposed or had been opened for 15 seconds or more, then vacuum and purge with field supplied refrigerant. Generally, do not remove plastic, rubber plugs and brass nuts from the valves, fittings, tubing and coils until it is ready to connect suction or liquid line into valves or fittings.
Piping Work & Flaring Technique TUBE D A (mm) Inch mm Imperial Rigid 1/4” 6.35 1.3 0.7 3/8” 9.52 1.6 1.0 1/2” 12.70 1.9 1.3 5/8” 15.88 2.2 1.7 3/4” 19.05 2.5 2.0 Piping Connection To The Units ó Align the center of the piping and tighten the flare nut sufficiently with fingers. ó Finally, tighten the flare nut with the torque wrench until the wrench clicks.
Vacuuming And Charging Method Purging the piping and the indoor unit The outdoor unit is equipped by two 3-way refrigerating connecting valves. The suction valve is the larger one whereas the smaller one is the liquid valve. Both valves are supplied with service port valve for connection to a manometer. ó ó ó ó ó ó ó ó ó ó ó ó Remove the caps from the valve and the service port. Connect the center manifold gauge to the vacuum pump. Connect the manifold gauge to the service port of the 3-way valve.
Additional Charge The refrigerant is pre-charged in the outdoor unit. If the piping length is less than 5m, then additional charge after vacuuming is not necessary. If the piping length is more than 5m, then use the additional charge valve as in the table below.
Overall Checking Ensure that: ó The unit has been mounted solidly and rigid in position. ó The piping and connections are leak-proof after the charging. ó Proper wiring has been installed. Drainage check ó Pour some water into the left side of the drain pan (the drainage is at the right side of the unit). Test run: ó ó ó ó ó ó Conduct a test run on the unit after having perform the water drainage test and the gas leakage test.
Remote Control Operation Guide Wireless Remote Control 1 AUTO 2 3 10 9 FAN 8 MODE S C 4 S TIMER ON C 5 TIMER OFF SLEEP SWING 6 7 1. Transmission source ó Source where the signal will be transmitted from. 2. Temperature setting ó Set the desired room temperature ó Press button to increase or decrease the set temperature. Setting range are between 16°C to 30°C (Optional setting from 20°C to 30°C ) 3. “ON/OFF” switch ó Press to start the air conditioner unit. ó Press again to stop the unit. 4.
Wired Remote Control 1. “ON/OFF” switch ó Press to start the air conditioner unit. ó Press again to stop the unit. 2. Temperature setting ó Set the desired room temperature. ó Press button to increase or decrease the set temperature. Setting range are between 16 °C to 30 °C (60 oF to 80 oF) 3. ó ó ó Operation modes Press the “MODE” button to select the type of operating mode. Cooling Only: COOL, DRY, FAN 4. Fan Speed selection ó Press the button until the desired fan speed is achieved. 5.
Standard Operation Conditions Temperature Ts (°C) Th (°C) Minimum indoor air temperature 19.4 13.9 Maximum indoor air temperature 26.7 19.4 Minimum outdoor air temperature 19.4 13.9 Maximum outdoor air temperature 46 24 Ts : Dry bulb temperature. Th : Wet bulb temperature. Start-up Open all valves to full open position and turn on power to the conditioner. 1. Set mode to “Cool”. Set the cooling temperature to the coolest position.
Servicing And Maintenance Warning Disconnect from the main supply before servicing the air conditioner unit. SERVICE PARTS MAINTENANCE PROCEDURES Indoor air filter 1.Remove any dust adhered on the filter by using a vacuum cleaner or wash in lukewarm water (below 40 °C) with neutral cleaning detergent. 2. Rinse well and dry the filter before placing it back onto the unit. 3.Do not use gasoline, volatile substances or chemical to clean the filter. At least once every 2 weeks. More frequently if necessary.
Maintenance 1. Normal maintenance on all conditioners is generally limited to filter changes. Lubrication of the fan motor is not required but may be performed to extend motor life. Use sae-20 non-detergent electric motor oil. 2. Filter changes are required at regular intervals. The time period between changes will depend upon the project requirements. Some applications such as motels produce a lot of lint from carpeting and linen changes, and will require more frequent filter changes.
Cleaning & Flushing System 1. Prior to first operation of any conditioner, the water circulating system must be cleaned and flushed of all construction dirt and debris. If the conditioners are equipped with water shut off valves, either electric or pressure operated, the supply and return run outs must be connected together at each conditioner location. This will prevent the introduction of dirt going into the unit. 2. Fill up the system at the city water makeup connection with all air vents open.
Troubleshooting When any malfunction of the conditioner unit is noted, immediately switch off the power supply to the unit. Check the following fault conditions and causes for some simple trouble shooting tips. FAULT POSSIBLE CAUSES 1. The compressor does not start operation after 3 ó Protection against frequent starting. Wait for 3 to 4 minutes from starting the air conditioner unit. minutes for the compressor to start operate. 2. The air conditioner unit does not operate.
The LED indicator on the control panel: FAN MODE SLEEP LED OFF OFF - Cooling AUTO HIGH MED LOW COOL DRY HEAT FAN OFF ONLY ONE ON ON OFF OFF Status Analysis ON ONLY ONE ON ON OFF OFF OFF OFF - Auto fan cooling OFF OFF OFF OFF OFF ON OFF OFF OFF - Dry mode OFF ONLY ONE ON OFF OFF ON OFF OFF - Heating ON ONLY ONE ON OFF OFF ON OFF OFF - OFF ONLY ONE ON OFF OFF OFF ON OFF - Auto fan heating ON ONLY ONE ON OFF OFF OFF ON OFF
REGISTERED S&E ©2002 McQuay International +1 (800) 432-1342 www.mcquay.