TEMPERATURE SETTING
• Set the desire room
temperature.
• Press button to increase
or decrease the set
temperature. Setting
range are between 16°C
to 30°C setting (60°F to
80°F)(Optional setting
from 20°C to 30°C).
• Press 5 or 6 button
simultaneously will toggle
the temperature setting
between °C and °F.
ON / OFF switch
• Press to start the air
conditioner unit.
• Press again to stop the
unit.
SIGNAL TRANSMISSION
INDICATION
• Blink to confirm the last setting
has been send to the unit.
FAN SPEED AND
VENTILATION MODE
SELECTION
• Press the button until the
desired fan speed is
achieved.
OPERATION MODES
• Press the “mode” button
for select the type of
operating mode.
• Cooling only unit:
Cool→Dry→Fan.
• Heating cycles:
Cool→Dry→Heat→Fan.
TIMER SETTING
• Press set button to
activate the timer setting
(from 1 hour to 15 hour)
of the air conditioning
unit. It will be in "On" or
"Off" condition after the
set time depending to
the current condition
(either from "On" to Off"
or vise versa)
• To cancel the timer
setting, press the button
continuously until the
timer display goes off.
SLEEP MODE
•
Press the button to activate sleep mode.
This mode can only be activated while in
cooling or heating mode operation. If it is
activated in “COOL” mode, the set
temperature will be increase 0.5°C after
30
minutes, 1°C after 1 hour and 2°C
after 2 hours.
AUTOMATIC AIR SWING
• Press the button to
activate the automatic air
swing function. The
swing angle ranging from
horizontal to 25° to
bottom.
ControllersControllers
TYPE OF CONTROLLER VS TYPE OF FAN COIL
MODELS STANDARD CONTROLLER OPTIONAL CONTROLLER
MCK020~050AW G6 WIRELESS CONTROL NETWARE 2 CW (WIRED CONTROLLER)
MCM020~050DW G6 WIRELESS CONTROL NETWARE 2 CW (WIRED CONTROLLER)
MCC010~060CW
NETWARE 2 CW (WIRED
CONTROLLER)
-
MDB075~150BW WITHOUT CONTROLLER -
SELF DIAGNOSIS TABLE
Wireless Wired
Power LED Other LEDs 7 Segment Display
Operation / Faulty Indication
Blinks 4 times Fan blinks E1 Blinking Room sensor contact loose / short
Blinks 4 times Sleep blinks E2 Blinking Indoor coil sensor contact loose / short
Blinks 1 time Cool blinks E4 Blinking Pipe water temperature fault
Blinks 2 times Cool & Fan blinks E6 Blinking Pump faulty
OPERATION GUIDE FOR G6
7
6
2
8
3
1
4