Specifications
16
Correction FactorsCorrection Factors
ALTITUDE CORRECTION FACTORS
Elevation, m Total Capacity Sensible Capacity
0 1.00 1.00
300 0.99 0.96
600 0.98 0.93
900 0.97 0.90
1200 0.96 0.86
1500 0.94 0.83
1800 0.93 0.80
HEATING CAPACITY CORRECTION FACTORS
ENTERING TEMPERATURE, °C
EAT
°C
37.8 43.3 45.0 48.8 54.4 60.0 65.5 71.1 76.7 82.2 87.7
4.4
0.838 0.980 1.021 1.122 1.265 1.406 1.552 1.698 1.845 1.988 2.134
7.2
0.771 0.913 0.954 1.055 1.198 1.379 1.485 1.631 1.778 1.920 2.067
10.0
0.700 0.843 0.885 0.986 0.130 1.272 1.417 1.563 1.710 1.853 2.000
12.7
0.631 0.773 0.817 0.918 1.062 1.205 1.349 1.495 1.639 1.786 1.931
15.5
0.562 0.705 0.748 0.848 0.992 1.137 1.281 1.427 1.572 1.719 1.865
18.3
0.493 0.636 0.679 0.779 0.923 1.070 1.212 1.358 1.504 1.650 1.799
21.1
0.424 0.567 0.610 0.711 0.855 1.000 1.146 1.290 1.438 1.583 1.730
23.9
0.354 0.498 0.541 0.642 0.786 0.932 1.078 1.222 1.369 1.515 1.664
26.7
0.284 0.428 0.471 0.573 0.717 0.863 1.008 1.155 1.302 1.449 1.597
Notes : Adjusted capacity, W (@ Nominal air flow) = base heating capacity (@ nominal 60°C EWT, 21.1°C EAT) x Heating Capacity
Correction Factor