Specifications
Model : MCK030B / MLC030B 
Indoor DB  Indoor WB  Capacity  Outdoor DB, ° C 
° C  ° C  kW  19.4  25  30  35  40  46 
26.7 13.9 TC 6.802 6.553 6.33 6.108 5.885 5.618 
    SC  6.802 6.553 6.33 6.108 5.885 5.618 
  15  TC  7.619 7.206 6.838 6.469  6.1 5.658 
    SC  6.593 6.339 6.113 5.887 5.661 5.39 
  18  TC  9.849 8.989 8.221 7.454 6.686 5.765 
    SC  6.022 5.758 5.522 5.286 5.051 4.768 
  19.4  TC  10.889 9.821 8.867 7.913 6.959 5.815 
    SC  5.756 5.486 5.246 5.006 4.766 4.477 
  20  TC  11.335 10.226  9.235  8.244  7.254 6.065 
    SC  5.641 5.366 5.121 4.875 4.629 4.335 
  22  TC  12.822 11.574 10.461  9.348  8.234 6.898 
    SC  5.261 4.966 4.702 4.439 4.176 3.859 
  24  TC  14.308 12.923 11.687 10.451 9.215 7.731 
    SC  4.881 4.565 4.284 4.003 3.722 3.384 
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB,   
please use the formula below :   
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000   
Where,  BPF = Bypass factor 
  EDB = Entering dry bulb temperature, ° C 
MCK015B 
MLC015B 
MCK020B 
MLC020B 
MCK025B 
MLC025B 
MCK030B 
MLC030B 
Bypass factor 0.67 0.16 0.26 0.21 
31 