Specifications

109
9. Refrigerant Piping
A) Maximum Pipe Length and Maximum Number of Bends
Always choose the shortest path for refrigerant piping and follow the recommendation as tabulated below:
Remarks: The refrigerant pre-charged in the outdoor unit is for piping length up to 7.62m/25ft.
B) Flare Connection
Cut the pipe stages by stages, advancing the blade of pipe cutter slowly.
Remove burr with the burr remover. Hold the flaring end down to prevent burrs from dropping inside
pipe.
Model M5LCX 010C/CR M5LCX 015C/CR M5LCX 020C/CR M5LCX 025C/CR
Maximum length, L (m/ft) 15/49 15/49 30/98 30/98
Max. elevation, H (m/ft) 5/16.4 5/16.4 8/26.2 8/26.2
Max. number of 90° bends 10 10 10 10
Liquid pipe size ¼” ¼” ¼” ¼”
Gas pipe size
3
/
8
½” ½”
5
/
8