Instruction manual
IM-5WMF(SEER13)-0706             Page 11 
Electrical Connections 
• Wiring must be in accordance with all applicable 
electrical codes. 
• Wires must not touch the refrigerant piping, 
compressor or any moving part. 
• All electrical field wiring must be clamped at both the 
indoor unit and the outdoor unit. See Figure 14 for 
typical clamp. 
•  See Table 4, figure 13 and Figure 15 for the number 
of wires, wire gauge and fuse/circuit breaker size 
required. 
Table 4: Wire and Fuse/Breaker Requirements 
10/15 
Unit Size 
Indoor Outdoor 
20/25 
Voltage-1Ph/60Hz 
115V 208/230V 208/230V
Power supply wire size 
Number of wires 
14 ga. 
2 + gnd. 
14 ga. 
2 + gnd. 
12ga. 
2 + gnd. 
Connecting wire size 
Number of wires – A/C 
Number of wires - HP 
14 ga. 
2 
4 
14 ga. 
3 + gnd. 
5 + gnd. 
Fuse/Breaker size 
15 amp  15 amp  20 amp 
* Not including the Outdoor Coil Sensor Cable. 
Figure 13. Cooling Only Size 10 & 15 
Indoor Unit     Outdoor Unit 
Terminal Block Connecting Wires Terminal Block 
COMP 
N2 
N1 
L 
NEC requires an approved 
electrical disconnect within sight 
of the unit so that anyone 
working on the unit can turn the 
power off and see that its not 
accidentally turned back on. This 
will require two disconnects, one 
by the outdoor unit and one by 
the indoor unit. 
COMP 
N2 
N1 
L 
Power 
supply 
208/230V 
!
L2 
L1 
N 
L1 
Power 
supply 
115V 
Figure 14. Terminal Block and wire Clamp 
Figure 15. Heat Pump Unit Size 10 & 15 
4WV 
OF 
Comp 
N2 
N1 
L 
4WV 
OF 
Comp 
N2 
N1 
L 
!
Power 
supply 
208/230V 
L2 
L1 
N 
L1 
Power 
supply 
115V 
Outdoor coil sensor, 2 conductor cable, (26 feet long) 
shipped with the indoor unit. Extend with 22 ga. low voltage 
wire if not long enough to reach outdoor unit. 
Indoor Unit 
Terminal Block 
Outdoor Unit 
Terminal Block 
Connecting Wires 
NEC requires an approved 
electrical disconnect within 
sight of the unit so that 
anyone working on the unit 
can turn the power off and 
see that its not accidentally 
turned back on. This will 
require two disconnects, one 
by the outdoor unit and one 
by the indoor unit 
WARNING 
!
Improper installation can cause severe personal 
injury or death. Wiring must be done by a qualified 
electrician in compliance with local codes. Model 
10F, 10FR, 15F and 15FR are using two separate 
power supply. Indoor unit powered by 
115V/1Ph/60Hz. Outdoor unit powered by 208-
230V/1Ph/60Hz. 