Specifications
Yes 
Variable compressor high discharge temperature (Comp 1 discharge overheat) 
Compressor stops 
> 110°C? 
To check & rectify 
Yes 
Is Temp. sensor 
ok? (<100°C?) 
Sensor faulty 
Check the Air-
Cond. system for 
high discharge 
tem
p
.
System high discharge pressure 
To replace sensor 
To rectify 
No 
Yes 
Yes 
Yes 
Yes 
No 
Fixed compressor over-current (Comp.2 overload) 
Compressor faulty 
Check on 
compressor 
winding 
resistance, is it to 
spec? 
To replace compressor 
Yes 
Check on 
compressor 
insulation, is it 
ok? 
Compressor shorted 
Is supply voltage 
ok? 
Supply voltage failure 
To replace compressor 
To rectify 
No 
No 
Yes 
Check current 
reading on 
handset against 
actual reading, is it 
very big different? 
Normal 
No 
Current sensing circuit error 
To replace Main board 
90