Specifications
88
Is heat sink 
temperature 
>100°C? 
No 
IPM Error 
IPM faulty 
Is IPM ok? 
To replace IPM 
Yes 
Is current at rated 
frequency ok? 
Compressor faulty  
Is IPM Error 
persists? 
Normal 
To check & rectify 
Heat sink condition improper 
Main board faulty or wrong signal 
To rectify 
No 
Is IPM temperature 
>100°C? 
Heat compound dried out 
Yes 
No 
Yes 
No 
Yes 
No 
Yes 
To rectify / replace 
To replace and re-apply 
Is heat compound 
dried out? 
IPM faulty 
No 
To replace IPM 
Yes 