Specifications
6.2.7 Advance Parameter Settings
The Chiller Panel provide user a lot of advance parameter settings for the Chiller. The parameters are
divided into 7 groups. There all are stored in [Set Parameter] menu and it is password-protected layer
in the panel.
* CAUTION : INPROPER SETTINGS WILL CAUSE PERMANENT DAMAGE TO THE CHILLER !!!
7 groups of Advance Parameter:
1) General
2) Regulator
27
 <ENTER>  <ENTER>
Summary Pages Main Menu Settings Menu
 <ESC>  <ESC>
<ENTER> <ESC> 
 Key in Password
Set Parameter
R1 Cool SP  : 12.0°C 
R2 Cool Diff  : 3.0°C 
R3 Heat SP  : 40.0°C 
R4 Heat Diff  : 3.0°C 
R5 Min Cool SP  : -20°C 
R6 Max Cool SP : 40°C 
R7 Min Heat SP  : -20°C 
R
8 Max Heat SP : 90°C 
R9 Ax Heat SP  : 5.0°C 
R10 Ax Heat Diff : 2.0°C 
R11 Au Bo SP  : 5.0°C 
R12 Au Bo Diff  : 2.0°C 
R13 Au Bo Start : 30m 
G1 Mode  : Chiller 
G2 No. Comp  : 1 Comp 
G3 On/Off in  : Disable 
G4 Cool/Heat in  : Disable 
G5 Ext Alarm in  : Disable 
G6 Water sys  : Isolated 
G7 Unit No  : 0 