Specifications
6.2.5 Changing Mode Set Temperature
There are 2 ways to change the mode set temperature for the Chiller.
i) [Operation Menu]
25
 <ENTER>  <ENTER>
 Summary Pages Main Menu Operation Menu
 <ESC>  <ESC>
In [Operation Menu], select “Cool Temp” / “Heat
Temp”and press ENTER start setting or ESC to exit
to [Main Menu].
Change value via UP or DOWN button, and then press
ENTER to confirm the change or ESC to cancel.
In [Set Parameter], select “Regulator” and press
ENTER. Press ESC to exit to [Main Menu].
Select “R3”/ “R5” and press ENTER to start setting
or ESC to exit to [Set Parameter] menu.
Change value via UP or DOWN button. The
boarderline is limited by R5&R6 (cool), R7&R8(heat).
Press ENTER to confirm or ESC to cancel.
  OPERATION MENU 
Status  : ON 
Mode  : Cooling 
Cool Temperature  : 12.0° C 
Heat Temperature  : 40.0° C 
  OPERATION MENU 
Status  : ON 
Mode  : Cooling 
Cool Temperature  : 12.0° C 
Heat Temperature  : 40.0° C 
1. General 
2. Regulator 
3. Compressor 
4. Defrost 
5. Antifreeze 
6. Inverter 
7. Alarm and Contact 
R1 Cool SP  : 12.0°C 
R2 Cool Diff  : 3.0°C 
R3 Heat SP  : 40.0°C 
R4 Heat Diff  : 3.0°C 
R5 Min Cool SP  : -20°C 
R6 Max Cool SP : 40°C 
R7 Min Heat SP  : -20°C 
R1 Cool SP  : 12.0°C 
R2 Cool Diff  : 3.0°C 
R3 Heat SP  : 40.0°C 
R4 Heat Diff  : 3.0°C 
R5 Min Cool SP  : -20°C 
R6 Max Cool SP : 40°C 
R7 Min Heat SP  : -20°C 