Specifications
31
M4MST SERIES COOLING ONLY
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO  ARI 210/240-94.
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
4) SOUND PRESSURE LEVEL IS ACCORDING TO JIS B 8615 STANDARD.
 POSITION OF THE MEASUREMENT POINT IS 1.0m IN FRONT AND 1.0m BELOW THE UNIT.
5) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.
MODEL OUTDOOR UNIT M4MST101010A M4MST151515A
INDOOR UNIT
3 x MWMS010G 2 x MWMS010G MWMS015G MWMS010G 2 x MWMS015G 3 x MWMS015G
kcal/h
3 x 2268 2 x 2268 3024 2268 2 x 3024 3 x 3024
W
3 X 2638 2 X 2638 3517 2638 2 x 3517 3 x 3517
Btu/h
3 X 9000 2 X 9000 12000 9000 2 x 12000 3 x 12000
RATED TOTAL POWER CONSUMPTION W
2580 4161
RATED TOTAL RUNNING CURRENT A
11.1 19.0
POWER SOURCE  V/Ph/Hz
REFRIGERANT / CONTROL
FAN TYPE
HIGH CFM/LPS
300 / 141.6 300 / 141.6 345 / 162.82 300 / 141.6 345 / 162.82 345 / 162.82
MEDIUM CFM/LPS
250 / 117.99 250 / 117.99 285 / 134.51 250 / 117.99 285 / 134.51 285 / 134.51
LOW CFM/LPS
200 / 94.39 200 / 94.39 220 / 103.83 200 / 94.39 220 / 103.83 220 / 103.83
FAN MOTOR 4P x 9W 4P x 9W 4P x 13W 4P x 9W 4P x 13W 4P x 13W
INPUT POWER W
26 26 29 26 29 29
RUNNING CURRENT A 0.11 0.11 0.13 0.11 0.13 0.13
FAN MOTOR PROTECTION
MATERIAL
DIAMETER mm/in
THICKNESS mm/in
MATERIAL
THICKNESS mm/in
ROW
FIN PER INCH
FACE AREA
m
2
/
ft
2
HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
WEIGHT kg
SOUND PRESSURE LEVEL ( H/M/L )  dBA 39 / 34 / 28 39 / 34 / 28 42 / 36 / 29 39 / 34 / 28  42 / 36 / 29 42 / 36 / 29
ROOM TEMPERATURE
CONTROL AIR DISCHARGE
OPERATION
CONDENSATE DRAIN SIZE mm/in
AIR FILTER 
PACKING HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
957 / 37.7
270 / 10.6
LCD WIRELESS MICRO COMPUTER REMOTE CONTROL 
16 / 0.63
WASHABLE SARANET
337 / 13.3
198 / 7.8
12
MICROCOMPUTER CONTROLLED THERMOSTAT  
AUTOMATIC LOUVER (UP & DOWN) & MANUAL ADJUST GRILLE (LEFT & RIGHT) 
0.234 / 2.516
260 / 10.2
899 / 35.4
7.0 / 0.276
0.28 / 0.011
FIN
A
LUMINIUM 
(
HYDROPHILIC SLIT FIN
)
 0.11 / 0.0043
2
18
220 ~ 240/1/50
R407C / OUTDOOR CAPILLARY TUBE
INDOOR UNIT
FAN
ANTI FUNGUS CROSS FLOW TANGENTIAL FAN / DIRECT
AIR FLOW 
THERMAL OVERLOAD
COIL
TUBE
SEAMLESS INNER GROOVED COPPER
CAPACITY
3107 3634
13.8 16.5
M4MST101015A M4MST101515A
NOMINAL 
COOLING
COMPRESSOR TYPE
NUMBER
CAPACITOR µF
LOCK ROTOR AMP A
20 20 25 20 25 25
INPUT POWER W 758 758 1282 758 1282 1282
PROTECTION DEVICE
FAN TYPE / DRIVE
BLADE MATERIAL
DIAMETER mm/in
RATED RUNNING CURRENT A 
W 
RATED INPUT POWER  W
AIR FLOW  CFM/LPS
MATERIAL
DIAMETER mm/in
THICKNESS mm/in
MATERIAL
THICKNESS mm/in
ROW
FIN PER INCH
FACE AREA
m
2
/
ft
2
HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
WEIGHT kg 97 109
SOUND PRESSURE LEVEL dBA
MATERIAL
CASING THICKNESS mm/in
FINISHING
TYPE
SIZE LIQUID mm/in
GAS mm/in
9.52 / 3/8 9.52 / 3/8 12.7 / 1/2 9.52 / 3/8 12.7 / 1/2 12.7 / 1/2
PACKING HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
REFRIGERANT CHARGE kg 3 x 0.750 2 x 0.750 0.775 0.750 2 x 0.775 3 x 0.775
1194 / 47.0
611 / 24.1
PIPE 
FLARE VALVE
6.35 / 1/4
824 / 32.4
65
GALVANISED MILD STEEL
1.0 - 1.2 / 0.039 - 0.047
EPOXY-POLYESTER POWDER
960 / 37.8
437 / 17.2
101 105
3
14
0.50 / 5.39
631.7/24.9
228
2400 / 1133
COIL
TUBE
SEAMLESS COPPER
9.52 / 3/8
0.35 / 0.014
FIN
ALUMINIUM (SLIT FIN TYPE)
0.12 / 0.005
GLASS REINFORCED ACRLY STYRENE RESIN
486.2 / 19
0.98
MOTOR OUTPUT 
150
OUTDOOR UNIT
COMP
ROTARY
3
30
OVERLOAD PROTECTION
FAN
PROPELLER / DIRECT