Specifications

28
M4MSD SERIES HEATPUMP UNIT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING CAPACITY IS BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35°C DB OUTDOOR
b) HEATING - 21.1°C DB / 15.6°C WB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR
4) SOUND PRESSURE LEVEL IS ACCORDING TO JIS B 8615 STANDARD.
POSITION OF THE MEASUREMENT POINT IS 1.0m IN FRONT AND 1.0m BELOW THE UNIT.
5) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR CONFIRMATION.
MODEL OUTDOOR UNIT
INDOOR UNIT
MWMS010GR MWMS010G
R
MWMS010GR MWMS015GR MWMS015G
R
MWMS015GR
NOMINAL kcal/h
2268 / 2268 2772 / 2646
COOLING W
2638 / 2638 3224 / 3077
CAPACITY Btu/h
9000 / 9000 11000 / 11500
NOMINAL kcal/h
2394 / 2668 3024 / 2898
HEATING W
2784 / 2638 3517 / 3370
CAPACITY Btu/h
9500 / 9000 12000 / 11500
ONE UNIT RUNNING W
994 994 994 1466 1466 1466
TWO UNITS RUNNING W
ONE UNIT RUNNING W
992 992 992 1476 1476 1476
TWO UNITS RUNNING W
ONE UNIT RUNNING A
4.21 4.21 4.21 6.71 6.71 6.71
TWO UNITS RUNNING A
ONE UNIT RUNNING A 4.21 4.21 4.21 6.71 6.71 6.71
TWO UNITS RUNNING A
POWER SOURCE
V
/Ph/Hz
REFRIGERANT / CONTROL
FAN TYPE
HIGH CFM/LPS
300 / 141.6 345 / 162.82
MEDIUM CFM/LPS
250 / 117.99 285 / 134.51
LOW CFM/LPS
200 / 94.39 220 / 103.83
FAN MOTOR
RATED INPUT POWE
R
W
26 29
RATED RUNNING CURRENT A
0.11 0.13
FAN MOTOR PROTECTION
MATERIAL
DIAMETER mm/in
THICKNESS mm/in
MATERIAL
THICKNESS mm/in
ROW
FIN PER INCH
FACE AREA
m
2
/ft
2
HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
WEIGHT kg
SOUND PRESSURE LEVEL ( H/M/L ) dB
A
39 / 34 /28 42 / 36 / 29
ROOM TEMPERATURE
CONTROL AIR DISCHARGE
OPERATION
CONDENSATE DRAIN SIZE mm/in
AIR FILTER
PACKING HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
WASHABLE SARANET
337 / 13.3
957 / 37.7
270 / 10.6
MICROCOMPUTER CONTROLLED THERMOSTAT
A
UTOMATIC LOUVER (UP & DOWN) & MANUAL ADJUST GRILLE (LEFT & RIGHT)
LCD WIRELESS MICRO COMPUTER REMOTE CONTROL
16 / 0.63
198 / 7.8
12
39 / 34 / 28 42 / 36 / 29
18
0.234 / 2.516
260 / 10.2
899 / 35.4
THERMAL OVERLOAD RELAY
COIL
TUBE
SEAMLESS INNER GROOVED COPPER
7.0 / 0.276
0.28 / 0.011
FIN
A
LUMINIUM (HYDROPHILIC SLIT FIN)
0.11 / 0.0043
2
26 29
0.11 0.13
200 / 94.39 220 / 103.83
4 POLES X 9W 4 POLES X 13W
220 ~ 240 / 1 / 50
R407C / OUTDOOR CAPILLARY TUBE
INDOOR UNIT
FAN
A
NTI FUNGUS CROSS FLOW TANGENTIAL FAN / DIRECT
AIR FLOW
300 / 141.6 345 / 162.82
250 / 117.99 285 / 134.51
RATED RUNNING
CURRENT (HEATING)
7.20 9.22
11.04
RATED RUNNING
CURRENT (COOLING)
7.60 9.52
11.24
RATED POWER
CONSUMPTION
(HEATING)
1,690 2,044 2,398
RATED POWER
CONSUMPTION
(COOLING)
1,800 2,139 2,478
ONE / TWO UNIT
RUNNING
2394 / 2668 3024 / 2898
2784 / 2638 3517 / 3370
9500 / 9000 12000 / 11500
M4MSD1010AR M4MSD1015AR M4MSD1515AR
ONE / TWO UNIT
RUNNING
2268 / 2268 2772 / 2646
2638 / 2268 3224 / 3077
9000 / 9000 11000 / 11500
COMPRESSOR TYPE
NUMBER
CAPACITO
R
µ
F 30 30 30
LOCK ROTOR AMP A 20 32
PROTECTION DEVICE
FAN TYPE / DRIVE
BLADE MATERIAL
DIAMETER mm/in
RATED RUNNING CURRENT A
RATED OUTPUT POWER W
RATED INPUT POWE
R
W
MATERIAL
DIAMETER mm/in
THICKNESS mm/in
MATERIAL
THICKNESS mm/in
ROW 2
FIN PER INCH
FACE AREA
m
2
/
ft
2
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
k
g
SOUND PRESSURE LEVEL dB
A
54
MATERIAL
THICKNESS mm/in
FINISHING EPOXY-POLYESTER POWDER
TYPE FLARE VALVE
SIZE LIQUID mm/in
GAS mm/in
9.52 / 3/8 12.7 / 1/2
PACKING HEIGHT mm/in
DIMENSION WIDTH mm/in
DEPTH mm/in
k
g
0.750 0.800
710 / 28.0
982 / 38.7
461 / 18.1
REFRIGERANT CHARGE
2 x 0.725 2 x 0.800
CASING
GALVANISED MILD STEEL
0.8 / 0.031
PIPE
6.35 / 1/4
9.52 / 3/8 12.7 / 1/2
WEIGHT
63 64 65
0.51 / 5.53
DIMENSION
646 / 25.4
840 / 33.1
330 / 13
170
COIL
TUBE
SEAMLESS INNER GROOVED COPPER
9.52 / 3/8
0.33 / 0.013
FIN
A
LUMINIUM (SLIT FIN TYPE)
0.12 / 0.005
16
GLASS REINFORCED ACRLY STYRENE RESIN
406 / 16
0.72
80
OUTDOOR UNIT
COMP
ROTARY
2
30
20 32
OVERLOAD PROTECTION
FAN
PROPELLER/DIRECT